AC300 Series Vector Control Inverter Manual
Function Parameter Specifications
138
Multi-speed terminal
4
Multi-speed terminal
3
Multi-speed terminal
2
Multi-speed terminal
1
terminal
speed
OFF OFF OFF ON 1X
[
F12.00
]
OFF OFF ON OFF 2X
[
F12.01
]
OFF OFF ON ON 3X
[
F12.02
]
OFF ON OFF OFF 4X
[
F12.03
]
OFF ON OFF ON 5X
[
F12.04
]
OFF ON ON OFF 6X
[
F12.05
]
OFF ON ON ON 7X
[
F12.06
]
ON OFF OFF OFF 8X
[
F12.07
]
ON OFF OFF ON 9X
[
F12.08
]
ON OFF ON OFF 10X
[
F12.09
]
ON OFF ON ON 11X
[
F12.10
]
ON ON OFF OFF 12X
[
F12.11
]
ON ON OFF ON 13X
[
F12.12
]
ON ON ON OFF 14X
[
F12.13
]
ON ON ON ON 15X
[
F12.14
]
inverter
X3
Multistep terminal 1
X4
Multistep terminal 2
X5
Multistep terminal 3
X6
Multistep terminal 4
X1 FWD/STOP
X2 REV/STOP
COM common terminal
K1
K2
K4
K3
K5
K6
Terminal connection
AC300 Series Vector Control Inverter Manual
Function Parameter Specifications
139
ON
ON
ON
ON
ON
ON
ON
ON
1X
2X
3X
4X
ON
5X
7X
ON
ON
8X
ON
ON
9X
10X
11X
ON
12X
ON
13X
ON
14X
15X
ON
6X
frequency
time
multi steps terminal 4(X6)
multi steps terminal 3(X5)
multi steps terminal 2(X4)
multi steps terminal 1(X3)
REV(X3)
FWD(X3)
MULTI STEP TIME ORDER
F12.15
PLC run mode selections
Setting range: 0000-2212
Factory set: 0000
Select PLC running mode while program given.
LED “0” digit: cycle mode
0: Stop after single cycle
While receiving order, inverter run from the first step, time unit is set by
[F12.15]
LED “00”
digit. Running time is set by
[F12.16-F12.30]
. Running direction and ACC/DEC time is selected by
[F12.31-F12.45]
.
Turn to next step while run time is over, run time, direction, ACC/DEC time of every step can be set separately. Inverter
output 0 Hz while finished 15 steps running. If one step running time is 0, it will skip this step.
1: Continuous cycles
Inverter not stop and runs at the latest speed while finished 15 steps running. Time unit is set
by
[F12.15]
LED “00” digit. Run time is set by
[F12.16-F12.30]
. Run direction and ACC/DEC time is selected by
[F12.31-F12.45]
.
2: Keep final value after single cycle
Inverter back to 1
st
step while finished 15 steps running. Time unit is set by
[F12.15]
LED “00” digit. Run time is set by
[F12.16-F12.30]
. Run direction and ACC/DEC time is selected by
[F12.31-F12.45]
.
Note: PLC ACC/DEC time is set by [F12.31-F12.45] LED “00”, and not be affected by terminal selection.