AC300 Series Vector Control Inverter Manual
Function Parameter Specifications
128
F10.17
Load pre alarm detection setting
Setting range: 0000~1414
Factory default: 0000
LED “0” digit: Detection selection (protection 1)
0: Not detected
1: Detected load is too large
2: Detected load is too large only at constant speed
3: Insufficient load detected
4: Insufficient load only at constant speed
LED “00” digit: Alarm selection
0: Alarm and continue operation
1: Fault protection and free stop
LED “000” digit: Detection selection (protection 2)
0: Not detected
1: Detected load is too large
2: Detected load is too large only at constant speed
3: Insufficient load detected
4: Insufficient load only at constant speed
LED “0000” digit: Alarm selection
0: Alarm and continue operation
1: Fault protection and free stop
F10.18
Load pre alarm detection level 1
Setting range: 0.0~200.0%
Factory default: 130.0%
F10.19
Load pre alarm detection time 1
Setting range: 0.0~60.0s
Factory default: 5.0s
F10.20
Load pre alarm detection level 2
Setting range: 0.0~200.0%
Factory default: 30.0%
F10.21
Load pre alarm detection time 2
Setting range: 0.0~60.0s
Factory default: 5.0s
In the VF control mode, the motor output current is used as the load warning judgment value, 100.0% corresponds to
the rated motor current; in the vector control mode, the motor output torque is used as the load warning judgment value,
100.0% corresponds to the rated output torque of the motor, and the load warning judgment value is The detection time
[F10.19/F10.21] is compared with the detection threshold [F10.18/F10.20], and the corresponding action is performed
according to [F10.17]. The alarm can be output through the terminal output. See Y Terminal function for details..
Check out the selection (Protection 1):
1: Detection load is too large
The running detection value is greater than [F10.18] load warning detection level 1 and the valid signal is output after
[F10.19] load warning detection time 1;
2: Excessive load detection only at constant speed
In the constant speed state, the detected value is greater than [F10.18] load warning detection level 1 and the valid
signal is output after [F10.19] load warning detection time 1;
3: Insufficient detection load
The running detection value is less than [F10.20] load warning detection level 2 and the valid signal is output after
[F10.21] load warning detection time 2;
4: Insufficient load detection only at constant speed
AC300 Series Vector Control Inverter Manual
Function Parameter Specifications
129
In the constant speed state, the detected value is less than [F10.20] load warning detection level 2 and the effective
signal is output after [F10.21] load warning detection time 2;
Checkout selection (Protection 2):
Same checkout selection (Protection 1)
F10.22 Reserved
F10.23
Protection action when speed slip is too large
Setting range: 0000-0012
Factory default: 0000
LED “0” digit: Detection selection
0: Not detected
1: Detected at constant speed
2: Detecting
LED “00” digit: Alarm selection
0: Free stop and report fault
1: Alarm and continue operation
LED “000” digit: Reserved
LED “0000” digit: Reserved
F10.24
detection threshold when speed slip is too large
Set range: 0.0-60.0%
Factory default: 10.0%
F10.25
detection time when speed slip is too large
Set range:0.0-60.0s
Factory default: 2.0s
Under VC control,if the speed feedback value and speed setting bias are more than detection threshold
[F10.24]
during the detection time
[F10.25],
inverter judges that the detection bias is too large and operate according to
[F10.23].
Speed bias detection threshold 100% corresponds to max frequency..
F10.26
Rapid protection action
Setting range: 0000-0012
Factory default: 0000
LED “0” digit: Detection selection
0: Not detected
1: Detected at constant speed
2: Detecting
LED “00” digit: Alarm selection
0: Free stop and report fault
1: Alarm and continue operation
LED “000” digit: Reserved
LED “0000” digit: Reserved
F10.27
Rapid detection threshold
Setting range: 0.0
~
150.0%
Factory default: 110.0%
F10.28
Rapid detection time
Setting range:0.000
~
2.000s
Factory default: 0.010s