106
C01-Malfunction Diagnosis Monitor Group
Press the PRG button for 2 seconds or more to enter the “C00” parameter group and press the up button to
enter the “C01” parameter group. Check the current status of the drive.
Function code
Function name
Unit and definition
Address
C01.00
Malfunction types
See fault code table
0x2200
C01.01
Malfunction diagnosis information
See fault code table
0x2201
C01.02
Malfunction running frequency
0.00
~
Max frequency
0x2202
C01.03
Malfunction output Voltage
0
~
1500V
0x2203
C01.04
Malfunction out Current
0.1
~
1000.0A
0x2204
C01.05
Malfunction Bus Voltage
0
~
3000V
0x2205
C01.06
Malfunction module temperature
0
~
100
℃
0x2206
C01.07
Malfunction machine state
LED “0” digit: Running direction
0: FWD 1: REV
LED “00” digit: Running status
0: Stop 1: ACC
2: DEC 3:Constant speed
LED “000” and “0000” digit :
Reserved
0x2207
C01.08
Malfunction input terminal status
See input terminal chart
0x2208
C01.09
Malfunction output terminal status
See output terminal chart
0x2209
C01.10
The last malfunction types
Please see malfunction code table
0x220A
C01.11
The first diagnosis information
Please see malfunction code table
0x220B
C01.12
The last malfunction running frequency
0.00~Maxfrequecy
0x220C
C01.13
The last malfunction output voltage
0
~
1500V
0x220D
C01.14
The last malfunction output current
0.1
~
2000.0A
0x220E
C01.15
The last malfunction bus voltage
0
~
3000V
0x220F
C01.16
The last malfunction module temperature
0
~
100
℃
0x2210
C01.17
The last malfunction machine state
LED “0” digit: Running direction
0: FWD
1: REV
LED “00” digit: Running status
0: Stop
1: Constant speed
2: ACC
3: DEC
LED “000” and “0000” digit :
Reserved
0x2211
C01.18
The last malfunction input terminal state
See input terminal chart
0x2212
C01.19
The last malfunction output terminal state
See output terminal chart
0x2213
C01.20
The first two malfunction types
Please see malfunction information
0x2214
C01.21
The first two diagnosis information
0x2215
AC300 Series Vector Control Inverter Manual
Function Parameter Specifications
107
C01.22
The first three malfunction types
code table
0x2216
C01.23
The first three diagnosis information
0x2217
F04.18
Keyboard display parameter 5
Same as above
Factory set: 0002
F04.19
Keyboard display parameter 6
Same as above
Factory set: 0004
F04.20
Keyboard display parameter 7
Same as above
Factory set: 001
F04.21
Keyboard display parameter 8
Same as above
Factory set: 0012
It is valid only when the keyboard is double-lined, and is used to display the parameter selection on the second line
of the keyboard. The two-line keyboard switches between the display parameters 5-8 of the second line of the keyboard
by the "
" key.
For details, see the parameters
[F04.14~F04.17].
F04.22
Keyboard display selections
Setting range: 0000-1111
Factory set: 0000
LED “0” digit: output frequency selection
0: Aim frequency Display the aim frequency of current control motor
1: Actual frequency Display the output frequency of inverter
LED“00” digit: Reserved
LED“000” digit: Power display dimension
To correct the output frequency of C-10.Can select the unit of the power
0: Power display ratio (%) Display the ratio of output power,100% corresponds with the rated motor power.
1: Power display Kilowatt (KW) Display the actual power
LED“0000” digit: reserved
F04.23
Monitor display
selection
LED “0” digit
: self-tuning display monitorin
g parameters
0: Invalid 1: Valid
LED “00” digit
: C05 group display selection
0-1: VF mode related parameters
2: VC mode related parameters
LED “000” digit
: C00.40~C00.69 display selection
0: Do not display 1: Display
Factory
default: 0000
F04.24
Rotate speed display coefficient
Setting range: 0.0-500.0%
Factory set: 100.0%
It sets the display coefficient of keyboard monitor item “machine speed” .100% is corresponding to motor rated
speed.
F04.25
Power display coefficient
Setting range: 0.0-500.0%
Factory set: 100.0%
This parameter sets the display coefficient ratio of the keyboard monitor item “output power”; for example, when the