80
11 Supplement
VEGAPULS 67 • Profibus PA
36533-EN-170405
Fig. 55: VEGAPULS 67: Block diagram with AI FB 1 … AI FB 3 OUT values
TB Transducer Block
FB 1 … FB 3
Function Block
Module of the PA sensors
For the cyclic data traffic, VEGAPULS 67 provides the following modules:
•
AI FB1 (OUT)
– Out value of the AI FB1 after scaling
•
AI FB2 (OUT)
– Out value of the AI FB2 after scaling
•
AI FB3 (OUT)
– Out value of the AI FB3 after scaling
•
Free Place
– This module must be used if a value in the data telegram of the cyclical data traffic should not
be used (e.g. replacement of temperature and Additional Cyclic Value)
A maximum of three modules can be active. By means of the configuration software of the Profibus
master you can determine the configuration of the cyclical data telegram with these modules. The
procedure depends on the respective configuration software.
Note:
The modules are available in two versions:
•
Short for Profibus master supporting only one "Identifier Format" byte, e.g. Allen
Bradley