6 Set up with the display and adjustment module
VEGAPULS 67 • Profibus PA
36533-EN-170405
4. Enter the suitable distance value in m for empty vessel (e.g. dis-
tance from the sensor to the vessel bottom) corresponding to the
percentage value.
5. Save settings with
[OK]
and move with
[ESC]
and
[->]
to the max.
adjustment.
Proceed as follows:
1. Select with
[->]
the menu item Max. adjustment and confirm with
[OK]
.
2. Prepare the percentage value for editing with
[OK]
and set the
cursor to the requested position with
[->]
.
3. Set the requested percentage value with
[+]
and save with
[OK]
.
The cursor jumps now to the distance value.
4. Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the min. distance to the antenna edge.
5. Save settings with
[OK]
The channel is the input selector switch for function block (FB) of
the sensor. Within the function block, additional scalings (Out-Scale)
are carried out. In this menu item, the value fir the function block is
selected:
•
PV (Primary Value):
– Linearised percentage value
•
SV1 (Secondary Value 1):
– Percent with radar, guided microwave and ultrasonic sensors
– Pressure or height with pressure transmitters
•
SV2 (Secondary Value 2):
– Distance with radar, guided microwave and ultrasonic sensors
– Percent with pressure transmitters
•
Height
Setup - Max. adjustment
Setup - AI FB1 Channel