55
6 Set up with the display and adjustment module
VEGAPULS 67 • Profibus PA
36533-EN-170405
In delivery status, the PIN is "
0000
".
In this menu item, the internal clock of the sensor is set.
When a reset is carried out, all settings (with only a few exceptions)
are reset. The exceptions are: PIN, language, lighting, SIL and HART
mode.
The following reset functions are available:
•
Delivery status:
Restoring the parameter settings at the time of
shipment from the factory incl. the order-specific settings. A cre-
ated false signal suppression, user-programmable linearization
curve, the measured value memory, echo curve memory as well
as event memory will be deleted.
•
Basic settings:
Resetting of the parameter settings incl. special
parameters to the default values of the respective instrument. Any
created false signal suppression, user programmable linearization
curve, measured value memory as well as event memory will be
deleted.
•
Setup:
Resetting of the parameter settings to the default values of
the respective instrument . Order-related settings remain but are
not taken over into the current parameters. User-generated false
signal suppression, user-programmed linearization curve, meas-
ured value memory, echo curve memory as well as event memory
remain untouched. The linearization is set to linear.
•
False signal suppression:
Deletes a previously created false
signal suppression. The false signal suppression created at the
factory remains active.
•
Peak values, measured value:
Resets the measured min. and
max. distances to the current measured value.
Select the requested reset function
[->]
and confirm with
[OK]
.
The following table shows the default values of VEGAPULS 67: