43
6 Set up with the display and adjustment module
VEGAPULS 67 • Profibus PA
36533-EN-170405
•
Process/measurement conditions:
– Condensation, buildup on the antenna
– Foam generation
•
Properties, sensor:
– Measurement speed optimized by virtually no averaging
– Sporadic false echoes are suppressed
– False signal suppression recommended
Standpipe:
•
Medium speed: very fast filling and emptying
•
Vessel:
– Vent hole
– Joins like flanges, weld joints
– Shifting of the running time in the tube
•
Process/measurement conditions:
– Condensation
– Buildup
•
Properties, sensor:
– Measurement speed optimized through little averaging
– Entering the tube inside diameter takes the running time shift
into consideration
– Echo detection sensitivity reduced
Bypass:
•
Medium speed:
– Fast up to slow filling with short up to long bypass tube possible
– Often the level is hold via a control facility
•
Vessel:
– Lateral outlets and inlets
– Joins like flanges, weld joints
– Shifting of the running time in the tube
•
Process/measurement conditions:
– Condensation
– Buildup
– Separation of oil and water possible
– Overfilling into the antenna possible
•
Properties, sensor:
– Measurement speed optimized through little averaging
– Entering the tube inside diameter takes the running time shift
into consideration
– Echo detection sensitivity reduced
– False signal suppression recommended
Plastic tank:
•
Vessel:
– Instrument fix mounted or built in
– Measurement through the vessel top, if appropriate to the
application
– With empty vessel, the measurement can go through the bot-
tom
•
Process/measurement conditions:
– Condensation on the plastic ceiling
– In outdoor facilities, water and snow on vessel top possible