5 Connecting to the bus system
VEGAPULS 67 • Profibus PA
36533-EN-170405
5.7 Wiring plan - version IP 66/IP 68, 1 bar
1
2
Fig. 34: Wire assignment in permanently connected connection cable
1 Brown (+) and blue (-) to power supply or to the processing system
2 Shielding
5.8 Set instrument address
An address must be assigned to each Profibus PA instrument. The
approved addresses are between 0 and 126. Each address must
only be assigned once in the Profibus PA network. The sensor is only
recognized by the control system if the address is set correctly.
When the instrument is shipped, address 126 is set. This address can
be used to test the function of the instrument and to connect it to a
Profibus PA network. Then the address must be changed to integrate
additional instruments.
The address setting is carried out either via:
•
The address selection switch in the electronics compartment of
the instrument (address setting via hardware)
•
The display and adjustment module (address setting via software)
•
PACTware/DTM (address setting via software)
The hardware addressing is effective if an address <126 is set with
the address selection switches on the instrument. Software address-
ing is then no longer effective, the set hardware address applies.
5
0
0
5
1
6
2
7
3
8
4
9
0
5
1
6
2
7
3
8
4
9
1
0
1
6 7 8
Bus
2
1
3
1 2
+
( )
(-)
Fig. 35: Address selection switch
1 Addresses <100 (selection 0), addresses >100 (selection 1)
2 Decade of the address (selection 0 to 9)
3 Unit position of the address (selection 0 to 9)
Wire assignment, con-
nection cable
Instrument address
Hardware addressing