40
6 Set up with the display and adjustment module
VEGAPULS 67 • Profibus PA
36533-EN-170405
Display:
Language setting, settings for the measured value indication
as well as lighting
Diagnosis:
Information, for example on the instrument status, pointer,
reliability, AI FB 1 simulation, echo curve
Further settings:
Instrument units, false signal suppression, lineari-
zation, sensor address, PIN, date/time, reset, copy sensor data
Info:
Instrument name, hardware and software version, date of manu-
facture, instrument features
In the main menu item "
Setup
", the individual submenu items
should be selected one after the other and provided with the correct
parameters to ensure optimum adjustment of the measurement. The
procedure is described in the following.
In the menu item "
Sensor TAG
" you edit a twelve-digit measurement
loop designation.
You can enter an unambiguous designation for the sensor, e.g. the
measurement loop name or the tank or product designation. In digital
systems and in the documentation of larger plants, a singular desig-
nation must be entered for exact identification of individual measuring
points.
The available digits include:
•
Letters from A … Z
•
Numbers from 0 … 9
•
Special char, -, /, -
Every medium has different reflective properties. With liquids, there
are additional interfering factors such as turbulent product surface
and foam generation. With bulk solids, the additional interfering fac-
tors are dust generation, angle of repose and secondary echoes from
the vessel wall.
To adapt the sensor to these different measuring conditions, the
selection "
Liquid
" or "
Bulk solid
" should be made in this menu item.
Through this selection, the sensor is optimally adapted to the product,
and measurement certainty, particularly in products with poor reflec-
tive properties, is considerably increased.
Setup - Measurement
loop name
Setup - Medium