41
6 Set up with the display and adjustment module
VEGAPULS 67 • Profibus PA
36533-EN-170405
Enter the requested parameters via the appropriate keys, save your
settings with
[OK]
and jump to the next menu item with the
[ESC]
and
the
[->]
key.
In addition to the medium, also the application, i.e. the measuring site,
can influence the measurement.
With this menu item, the sensor can be adapted to the applications.
The adjustment possibilities depend on the selection "
Liquid
" or "
Bulk
solid
" under "
Medium
".
The following options are available when "
Liquid
" is selected:
The selection "
Standpipe
" opens a new window in which the inner
diameter of the applied standpipe is entered.
Following the characteristics of the applications and the metrological
features of the sensor are described.
Note:
Probably the operation of the instrument in these applications is sub-
ject to national restrictions in respect to the radio license (see chapter
"
For your safety
"):
•
Plastic tank
•
Transportable plastic tank
•
Open water (gauge measurement)
•
Open flume (flow measurement)
•
Rain water overfall (weir)
Storage tank:
•
Setup: large-volumed, upright cylindrical, spherical
•
Medium speed: slow filling and emptying
•
Process/measurement conditions:
– Condensation
– Smooth product surface
– High requirements on measurement accuracy
•
Properties, sensor:
– Low sensitivity to sporadic false echoes
– Stable and reliable measured values through averaging
– High accuracy
– Short reaction time of the sensor not required
Setup - Application