6 Set up with the display and adjustment module
VEGAPULS 67 • Profibus PA
36533-EN-170405
2
1
3
0,5 m (19.68
")
10 m (393.7
")
100%
0%
Fig. 40: Parameterisation example, Min./max. adjustment
1 Min. level = max. measuring distance
2 Max. level = min. measuring distance
If these values are not known, an adjustment with the distances of e.g.
10 % and 90 % is possible. Starting point for these distance specifica-
tions is always the sealing surface of the thread or flange. You can find
specifications on the reference plane in chapter "
Technical data
". The
actual level is calculated on the basis of these settings.
The actual product level during this adjustment is not important,
because the min./max. adjustment is always carried out without
changing the product level. These settings can be made ahead of
time without the instrument having to be installed.
Proceed as follows:
1. Select the menu item "
Setup
" with
[->]
and confirm with
[OK]
.
Now select with
[->]
the menu item "
Min. adjustment
" and confirm
with
[OK]
.
2. Edit the percentage value with
[OK]
and set the cursor to the
requested position with
[->]
.
3. Set the requested percentage value with
[+]
and save with
[OK]
.
The cursor jumps now to the distance value.
Setup - Min. adjustment