CSLD Troubleshooting
Actual CSLD Test Problems Analyzed
11-30
T 3:PREMIUM UNLEADED
LAST HOUR = 248651
3737.9 3773.5 3797.8 3817.8 3883.3 3904.5 3904.7 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Analysis
The volume table IA53 gets cleared when a gap in time between probe samples is detected. The site operators
were turning the console’s power Off every evening. This caused a gap between probe readings which cleared the
volume table. CSLD does not perform any tests until the volume table is full (24 hours).
Solution
Keep power turned On to the console.
CSLD PROBLEM 8 - CSLD FAILURE TANK 1
Diagnostics
I25100
JUN 11, 1998 12:45 PM
Site Id 1
Site Id 2
Site Id 3
Site Id 4
CSLD TEST RESULTS
TANK PRODUCT RESULT
1 REGULAR PER: JUN 11, 1998 FAIL
2 PLUS PER: JUN 11, 1998 PASS
3 PREMIUM PER: JUN 11, 1998 PASS
200
Site Id 1
Site Id 2
Site Id 3
Site Id 4
JUN 11, 1998 12:45 PM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 REGULAR 6439 57.38 1.0 52.3 3289