11-21
11
CSLD Troubleshooting
Actual CSLD Test Problems Analyzed
Diagnostics
IA5402
JUN 24, 1996 2:30 PM
CSLD DIAGNOSTICS: MOVING AVERAGE TABLE
T 2: MIDGRADE
TIME
SMPLS
TLCVOL
HEIGHT
AVGTEMP
TOPTEMP
BDTEMP
960624140631
31 6521.67
53.299
78.76
81.10
86.64
960624140701
31 6521.77
53.298
78.72
80.99
86.54
960624140731
31 6521.85
53.297
78.67
80.88
86.44
960624140801
31 6522.22
53.298
78.61
80.75
86.34
960624140831
31 6522.67
53.298
78.53
80.62
86.23
960624140901
31 6523.02
53.298
78.46
80.49
86.11
960624140931
31 6523.44
53.299
78.38
80.35
85.94
960624141001
31 6523.48
53.297
78.30
80.17
85.81
960624141031
31 6523.90
53.297
78.22
80.04
85.67
960624141101
31 6524.77
53.301
78.15
79.93
85.84
960624141131
31 6524.58
53.298
78.11
79.84
85.41
960624141201
31 6525.14
53.301
78.09
79.77
85.28
960624141231
31 6524.94
53.299
78.08
79.71
85.15
960624141301
31 6524.97
53.299
78.06
79.66
85.03
960624141331
30 6525.22
53.300
78.04
79.62
84.91
960624141401
32 6525.17
53.299
78.02
79.57
84.79
960624141431
30 6525.26
53.299
77.98
79.51
84.68
960624141501
32 6525.63
53.299
77.93
79.24
84.52
960624141531
31 6526.39
53.302
77.68
79.33
84.40
960624141601
31 6526.71
53.303
77.80
79.26
84.29
960624141631
31 6526.88
53.302
77.74
79.20
84.17
960624141701
31 6527.34
53.304
77.72
79.17
84.07
960624141731
31 6527.60
53.306
77.73
79.17
83.97
960624141801
31 6527.49
53.308
77.81
79.27
83.89
960624141831
30 6527.37
53.311
77.93
79.43
83.85
960624141901
32 6526.21
53.307
78.05
79.62
83.82
960624141931
31 6526.36
53.311
78.16
79.78
83.81
960624142001
31 6525.02
53.305
78.23
79.94
83.81
960624142031
31 6525.20
53.307
78.26
80.00
83.81
960624142101
31 6524.84
53.304
78.25
80.01
83.80
960624142131
30 6523.02
53.304
78.25
80.00
83.80
960624142201
32 6526.39
53.314
78.23
80.04
83.79
960624142231
31 6526.65
53.319
78.35
80.19
83.81
960624142301
31 6525.05
53.315
78.57
80.45
83.86
960624142331
30 6523.43
53.319
78.84
80.78
83.94
960624142401
29 6521.88
53.310
79.11
81.12
84.05
960624142431
31 6519.58
53.303
79.34
81.44
84.17
960624142501
31 6519.59
53.308
79.53
81.69
84.35
960624142531
30 6518.62
53.304
79.60
81.84
84.47
960624142601
32 6518.72
53.305
79.59
81.90
84.58
960624142631
30 6519.02
53.305
79.53
81.89
84.67
960624142701
31 6519.54
53.305
79.43
81.78
84.73
960624142731
31 6520.18
53.307
79.35
81.70
84.78
960624142801
31 6520.59
53.308
79.31
81.66
84.83
960624142831
31 6519.95
53.305
79.33
81.68
84.88
960624142901
30 6519.45
53.304
79.41
81.79
84.95
MOVING AVERAGE: 6523.52
DISPENSE STATE: ACTIVE * 177.531143
Excessive differences may indicate a
defective probe.