background image

10-1

10  Sensor Troubleshooting

This section contains suggested corrective actions for troubleshooting sensor problems.

Turn off, tag, and lockout power to the console before opening display door assembly!

Sensor Alarm Will Not Clear

Liquid or fuel in containment area.

Sensor Out Alarms

Follow these steps in sequence to troubleshoot Sensor Out alarms.

1. Verify that the distance from the sensor to the TLS is less than 1000 feet. 

2. Verify that the sensor wiring conforms to the requirements detailed in the Site Prep and Installation Manual

(P/N 577014-073) and that it connects the console to the sensor.

3. Verify that the console grounding is correct. Make sure there are two grounds and that one is at least a 12 

AWG (or larger diameter) conductor. Check that the grounding conductors are properly connected to a good 
ground source. Measure the resistance to ground, it should be less than one ohm.

4. Verify that the console is on a separate circuit breaker with no shared branch circuits. 

5. Verify that the sensor connects to the proper connector position and that polarity (required for some sensors) is 

maintained from the sensor to the console. If necessary, refer to the Sensor Products Application Guide (P/N 
577013-750) for correct sensor/console compatibility and sensor specifications.

6. View the diagnostic screen for the problem sensor and search for information that may help you determine the 

root cause of the sensor’s problem.

7. Consider directly connecting the sensor to the console to confirm a faulty sensor.

Setup Data Warning

This alarm could be posted by one of three setup errors:

1. A label for the sensor was not entered during setup.

2. The wrong sensor type was selected during setup.

3. The sensor was not configured during setup but the console measures a resistive value and determines a 

device is connected.

Unstable Sensor Readings

Unstable sensor readings may be the result of intermittent signals or electro-magnetic interference (EMI). Some 
causes of unstable sensor readings are discussed below.

1. Shielded cable was not used between the sensor and the console, or if it was, it was not grounded correctly. 

See the Site Prep and Installation Manual

 

(P/N 577014-073) for installation requirements. 

2. Extra wires (not connected to the console) in the sensor conduit. They should be removed.

OFF

Summary of Contents for TLS-450PLUS

Page 1: ...Manual No 577014 075 Revision B Troubleshooting Guide TLS 450PLUS Console...

Page 2: ...r Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Contact Veeder Root Customer Service at 800 873 3313 with the specific part numbers and quantities that were missing or received damaged 2 Fax...

Page 3: ...c Screens 4 1 BIR 4 1 Available Diagnostic Screens 4 1 LPR Sensor 4 1 Available Line Pressure Sensor Diagnostic Reports 4 2 Mag Sensor 4 2 Available Mag Sensor Diagnostic Reports 4 2 Meter 4 2 Availab...

Page 4: ...XP Operating System 8 4 Using Putty And The TLSTECH Diagnostic Tool 8 6 TLSTECH Menu Examples 8 8 Menu selection 1 8 9 Menu selection 4 8 9 Menu selection 5 8 10 Menu selection 6 8 10 Menu selection...

Page 5: ...11 37 CSLD Problem 12 Periodic Test Fail on Tank 1 11 38 Figures Figure 2 1 Console Front Panel 2 1 Figure 2 2 Printer Door Assembly 2 2 Figure 2 3 Display Door Assembly 2 3 Figure 2 4 Console Board...

Page 6: ...Table 5 3 Liquid Sensor Alarms 5 5 Table 5 4 Vapor Sensor Alarms 5 6 Table 5 5 E xternal Input Alarms 5 6 Table 5 6 Groundwater Sensor Alarms 5 6 Table 5 7 Type A Sensor Alarms 5 7 Table 5 8 Type B S...

Page 7: ...77013 344 PLLD Troubleshooting Manual 577013 401 TLS Consoles Point of Sale POS Application Guide Contractor Certification Requirements Veeder Root requires the following minimum training certificatio...

Page 8: ...nti static wrist strap before handling the printed circuit board and mounted components READ ALL RELATED MANUALS Knowledge of all related procedures before you begin work is important Read and underst...

Page 9: ...5 T 15 Torx screws remove to open doors and access system components 7 Acknowledge ACK Switch panel 3 Right door 4 LED Status indicators System Nor mal Green X Warning Yellow Alarm Red 2 5 4 2 5 T 2 D...

Page 10: ...Printer Door Assembly Legend For Figure 2 2 Item Description Item Description 1 Paper roll release lever 4 Connector for data input cable to USB1 on CPU board 2 Printer assembly 5 Paper cover 3 Connec...

Page 11: ...play assembly 4 Cable to Ack Switch Panel connector on CPU board item 16 in Figure 2 11 2 Input Module Connection Labels 5 Cable to LED Backlight connector on CPU board item 11 in Figure 2 11 3 Cable...

Page 12: ...board 2 CPU board 5 AC Input board assembly access cover removed 3 I O Backplane board RELAY RATINGS RELAY RATINGS 240 VAC 2 A MAX 240 VAC 2 A MAX 24 VDC 2 A MAX 24 VDC 2 A MAX WARNING TO MAINTAIN INT...

Page 13: ...250V Slo Blo 2 Output relay control plugs into J3 on Power Supply board 6 AC Input board plugs into Power Sup ply board as shown 3 AC input power connector 4 Output relay control connector L2 J4 C1 L...

Page 14: ...ow voltage relay control connector Relay connector on AC input board connects here 4 Printer power supply fuse 3A Slo Blo 2 AC Input power connector Line AC input connector on AC input board connects...

Page 15: ...MM I O BACKPLANE SPARE 24V GND GND 24V EXT_RESET SNAP EXT_RESET 24V SLOT 1 GND GND SCREW GND SLOT 2 1 SNAP SNAP I O BACKPLANE 332616 001 332616 002 JJL012907 SLOT 3 1 SLOT 4 SNAP EXT_ GND GND 24V 24V...

Page 16: ...B62 B62 B1 B1 B12 B12 A62 A62 A12 A12 A1 A1 2 2 59 59 60 60 2 2 59 59 60 60 2 2 59 59 60 60 2 2 59 59 60 60 2 2 59 59 60 60 30 30 30 30 29 29 29 29 30 30 29 29 30 30 29 29 30 30 29 29 JJL 290807 JJL 2...

Page 17: ...erial NC C NC C NC C RS 232 Dual Port also EDIM Satellite S SAT and Satellite H JBox apps C C C C NC C RS 485 Single Port NC C NC C NC C RS 485 Dual Port C C C C NC C RS 232 RS 485 Dual Port C RS 232...

Page 18: ...is play 3 USB Type A connectors 2 12 Features iButton 4 Ethernet RJ 45 connectors 3 13 Backup Battery 5 USB 0 1 pitch header connectors 2 14 Configuration DIP switches 6 Display cable connector option...

Page 19: ...ons and requirements Configuration DIP Switch Settings Verify the Configuration DIP switches see item 14 in Figure 2 11 are set as shown below Figure 2 12 Configuration DIP Switch Settings Table 2 2 T...

Page 20: ...is one in which any spark or thermal effect is incapable of causing ignition of a mixture of flammable or combustible material in air under prescribed test conditions An intrinsically safe system is a...

Page 21: ...airing or replacing components a visual inspection of the overall condition of the system be made Turn off tag and lockout power to the console before starting this inspection 1 Inspect for signs of c...

Page 22: ...ion Fuse Size Type V R Part No F3 Printer 24V power supply Fuseholder Power Supply board 3A 250V Slo Blo 5 x 20 mm 576010 942 F4 Console 24V power supply Fuseholder Power Supply board 3A 250V Slo Blo...

Page 23: ...ufficiency This screen lets you view an histogram of the data collected at different levels of the tank for the tank s calibration Delivery Instructions This screen contains instructions to help you a...

Page 24: ...er AVAILABLE DIAGNOSTIC SCREENS Manual Mapping The Manual Mapping diagnostic screen will help you assign meters to tanks with small volume dispensing events and to identify post blend metering This sc...

Page 25: ...s they have data to display AVAILABLE PLLD DIAGNOSTIC REPORTS AND SCREENS 0 1 gph 0 38 lph Auto Confirm Report 0 1 gph auto confirm data 0 1 gph 0 38 lph Tests Report 0 1 gph diagnostics test results...

Page 26: ...SENSOR DIAGNOSTIC REPORTS Liquid diagnostic information about each Liquid Sensor Vapor diagnostic information about each Vapor Sensor Groundwater diagnostic information about each Groundwater Sensor...

Page 27: ...Table Report CSLD rate table CSLD Rate Test Report CSLD rate test results CSLD Test Status Report current CSLD test status SLD History Report all SLD test results SLD In Progress Reports SLD active te...

Page 28: ...eric Sensor Automatic Event Ae Contact Cn Comm Device Co Comm Comm Device Dispenser d Disp Dispenser EDIM CDIM LDIM E DIM EDIM CDIM LDIM External Input I ExtInp External Input Fueling Position Fp FPos...

Page 29: ...1 System Alarms Alarm Cause Action BIR Daily Close Pending Tanks are not idle Dispense or delivery is in progress BIR is waiting for an idle period to close the shift report BIR Shift Close Pending T...

Page 30: ...ciency is too low on the day before end of calibration period Extend the calibration period before it expires Alternatively let the calibration expire and then restart calibration Annual Leak Test Fai...

Page 31: ...ammed limit Stop delivery Do not allow additional delivery until product drops below preset limit Missing Delivery Ticket Warning Delivery Ticket information has not been entered at the console Enter...

Page 32: ...rea an outer wall rupture has occurred Call for service following the proce dures established for your site Liquid Warning Liquid reached 1 inch 25 4 mm on the dis penser pan or containment sump senso...

Page 33: ...rm Cause Action Generator Off Backup generator shut down in tank leak testing resumed None Generator On Backup generator switched on in tank leak testing halted None Input Alarm External device change...

Page 34: ...lem Recheck device setup parameters Water Alarm Water is present in the area being monitored by the sensor Call for service following the proce dures established for your site Table 5 8 Type B Sensor...

Page 35: ...ing halts if programmed to do so while the alarm is active Consult PLLD Alarm Quick Help Guide and PLLD diagnostic screens Line Equipment Alarm A problem with the pressure measurement equipment has be...

Page 36: ...ored parameter exceeded preset thresh old Call for service following the procedures established for your site Install Alarm Sensor not installed in correct position Call for service following the proc...

Page 37: ...data warning on depen dent device Relay or External Input prevents this device from working Call for service following the proce dures established for your site Setup Data Warning Device setup data p...

Page 38: ...ook settings for the con tact are correct fax address of recipient verify modem is configured Contact techni cal support for assistance Table 5 18 Auto Events Alarms Alarm Cause Action Setup Data Warn...

Page 39: ...On the rest are Off U Boot is loading the Operating System OS 4 All three LEDs On Linux is loaded and starts the drivers for USB Ethernet etc 5 The Green LED is On the rest are Off Linux is running a...

Page 40: ...roll into the paper tray with the end of the paper tail facing you from the bottom of the roll Pull the tail out and push the tail under the black paper feed roller until it exits above the feed rolle...

Page 41: ...e printer Replace printer door Defective printer communication module System will not com municate via fax Incorrect or defective interconnect cable Check cable between TLS and telephone jack Problem...

Page 42: ...Card mak ing sure it is in the position shown below and then reinsert it in its enclosure until it clicks into the enclo sure s latch Console Does Not Power On AC Power Input connector Item 3 Figure 2...

Page 43: ...ad SD card Replace SD card Bad CPU board Replace CPU board Acknowledge Ack Switch Not Working Properly The Ack cable plug is loose or not plugged in Ack connector Reseat cable connector Ack cable is b...

Page 44: ...lected Go to next cause No Communication Verify Node ID and IFSF messages displayed in Diagnostic Module IFSF screen On the front panel screen touch Menu Diagnos tics Module IFSF This screen allows yo...

Page 45: ...ected using DIP switches 1 4 using the legend below 6 Close the console door and reapply power 7 IFSF communication still not working go to next cause Intermittent communication Verify Termination DIP...

Page 46: ...plug with cable standoff and two small slots for Tie Wrap 2 conductor LON cable supplied by customer Cover snaps onto plug enclosing connections From the outside of the housing piece thread tie wrap u...

Page 47: ...connectors Ethernet communication settings such as IP Address type IP Address etc 1 Verify Ethernet communication settings are cor rect 2 Check if Ethernet port s Link and Activities LEDs are flashin...

Page 48: ...ng installed incorrectly 1 Open the Display door 2 Polarity is required for this device Locate the questionable probe s input wiring con nections at the USM connector Figure 2 7 on page 2 7 Verify the...

Page 49: ...page 2 10 Battery is installed in backwards with side of battery facing down in holder Remove the battery by gently lifting the retaining clip over the battery as you slide it to the right Reinstall...

Page 50: ...re con nected with white to terminal and black to termi nal item 1 in diagram below If three wire sensor verify the three wires are con nected as shown below item 2 in diagram below 3 Verify each of t...

Page 51: ...h the required features Bad Cyclic Redundancy CRC check sum error Replace CPU board Cannot Save Setup Data Data Retrieved Error Message In Sta tus Bar SD Card in write protect mode Remove the SD Card...

Page 52: ...type as indicated in Section 3 AC input board bad Replace AC input board Power supply board bad Replace Power supply board CPU board bad Replace CPU board Comm backplane board bad Replace Comm backpl...

Page 53: ...strap Part No 576010 908 included in your component replacement kit 6 Never slide parts over any surface 7 Avoid plastic vinyl and Styrofoam in your work area WARNING This console contains high voltag...

Page 54: ...w in the Backup Destination field to select the Backup thumb drive inserted in Step 1 then follow the on screen instructions to backup TLS 450PLUS console data Figure 7 2 DB Backup Screen 3 Turn off t...

Page 55: ...n Figure 2 1 2 For the Ack Switch panel door remove the Ack Switch Panel cable plug from its CPU board connector item 16 in Figure 2 11 on page 2 10 For the optional Display door remove the Display ca...

Page 56: ...ch Display Door 5 Remove the TLS 450PLUS Ack Switch Panel Display door by removing the top and bottom hinge shoulder screws see Figure 7 5 Figure 7 5 Remove Top And Bottom Optional Display Door Hinge...

Page 57: ...ress up releasing the CPU board from the snap pin Repeat at each of the remaining two retention pins 10 Tilt the board a little away from the bulkhead and grasping the edge of the board pull out firml...

Page 58: ...wly pull up and away from the Power Supply board until the two AC Input Filter plugs disconnect from the Power Supply board connectors Lift the AC Input Filter out of the console Remove the two T 15 s...

Page 59: ...of the board and lift the board up until it is free of the three snap pins item 2 in Figure 7 10 WARNING Shock hazard Do not touch underside of Power Supply board beneath the five capacitors identifi...

Page 60: ...board 13 Line up the three holes in the Power Supply board see item 2 in Figure 7 10 with the three retention pins in the back of the console housing and push the board down until the pins snap into...

Page 61: ...ly shield item 2 in Figure 7 9 over the Power Supply board and lower it down onto its two retention pins see item 2 in Figure 7 11 and snap it into place 17 Install the three T15 screws in the AC Inpu...

Page 62: ...he Power Supply board connector see Figure 7 13 Figure 7 13 Removing Printer Door Ground Wire 6 Remove the TLS 450PLUS Printer door by removing the top and bottom hinge shoulder T15 screws similar to...

Page 63: ...naps securely into the holder Removing The Features iButton 1 Perform all of the Steps in the section entitled Before Turning Off Power on page 7 2 2 Open the console doors as described in Step 1 of t...

Page 64: ...the Steps in the section entitled Before Turning Off Power on page 7 2 2 Open the console doors as described in Step 1 of the section entitled Removing The Ack Switch Panel Display Right Door And CPU...

Page 65: ...pointer 1 below 4 Wearing a static avoidance wrist strap grounded to the console push in on the small button pointer 2 above to release the plug latch and lift the small SATA drive board from the conn...

Page 66: ...rg uk sgtatham putty download html 2 Once in the site click on putty exe as shown below 3 Download putty exe to your desktop Before using putty and TLSTECH the laptop needs to be setup to connect to t...

Page 67: ...8 2 8 Console Diagnostics Using The TLSTECH Diagnostic Tool Reconfigure the Laptop PC Prior To Using TLSTECH 2 The Local Area Connection Status dialog box opens Click on the Properties button...

Page 68: ...rea Connection Properties dialog box highlight Internet Protocol Version 4 TCP IPv6 and then click the Properties button 4 In the Internet Protocol Version 4 TCP IPv4 Properties dialog box Check the U...

Page 69: ...have finished communicating with the TLS 450PLUS console you will have to reconfigure the laptop PC to its original TCP IP settings Repeat steps 1 4 above When the Internet Protocol Version 4 TCP IPv...

Page 70: ...s select Use the following IP address radio button and enter the Static IP address below this is the default IP address for the TLS 450PLUS console Once the IP address is entered click in the Subnet m...

Page 71: ...log box appears select the Obtain an IP address automatically radio button this selection is needed to connect to the internet and click the OK button Using Putty And The TLSTECH Diagnostic Tool 1 Dou...

Page 72: ...8 7 8 Console Diagnostics Using The TLSTECH Diagnostic Tool Using Putty And The TLSTECH Diagnostic Tool 4 When the login screen appears login as tlstech 5 Enter the password tlstech...

Page 73: ...s Enter TLSTECH Menu Examples The TLSTECH menu is shown below and examples of each menu item are shown below 1 Check status of apps 2 Take a system snapshot not yet implemented 3 Copy a snapshot to a...

Page 74: ...erver 2273 tlsuser WatchDog 2236 tlsuser MaintServer 1686 root httpd 21676 daemon _ httpd 29299 daemon _ httpd 26014 daemon _ httpd MENU SELECTION 4 Display system statistics Linux 2 6 35 3 433 g0fae9...

Page 75: ...s 0 frame 0 TX packets 440681 errors 0 dropped 0 overruns 0 carrier 0 collisions 0 txqueuelen 1000 RX bytes 142122262 135 5 MiB TX bytes 357490031 340 9 MiB Base address 0x2000 eth0 9 Link encap Ether...

Page 76: ...icmp_seq 1 ttl 127 time 0 404 ms 64 bytes from 10 20 77 5 icmp_seq 2 ttl 127 time 0 387 ms 10 20 77 5 ping statistics 3 packets transmitted 3 packets received 0 packet loss round trip min avg max std...

Page 77: ...ernet address 216 32 180 22 Server 10 28 54 15 Address 10 28 54 15 53 Non authoritative answer veeder com mail exchanger 10 mail global frontbridge com Authoritative answers can be found from mail glo...

Page 78: ...tfs rootfs 1 9G 1013M 742M 58 dev root ext3 1 9G 1013M 742M 58 tmpfs tmpfs 10M 4 0K 10M 1 dev tmpfs tmpfs 247M 228K 247M 1 tmp tmpfs tmpfs 247M 4 0K 247M 1 dev shm tmpfs tmpfs 247M 0 247M 0 run IO sta...

Page 79: ...ary Probe wired to wrong probe channel on probe module Verify probe is wired to correct chan nel Probe not sitting on bottom of tank Check and correct position of probe if necessary Fuel float stuck i...

Page 80: ...Conduit not grounded properly See Note 1 Non metallic conduit present See Note 1 Variable speed submersible pump in use See Note 1 Defective barrier board Replace barrier board Defective probe Replac...

Page 81: ...below 0 F or above 100 F Retest when product temperature is between 0 100 F Defective probe Replace probe Temp change error w 0 1 gph test Temp of fuel changed by more than 1 10th degree per hour duri...

Page 82: ...ires and the connecting field wiring These connections must have Veeder Root supplied epoxy packs on the splices Corroded splices will create Probe Out alarms If Veeder Root supplied epoxy packs are p...

Page 83: ...not magnetized This can be accomplished by using a metal paper clip on a string Dangle the paper clip suspended by a string into the probe riser to determine of the riser pipe is magnetized If the pap...

Page 84: ...o 0 985 0 985 3 Density Mag Probes Form Number 8860 D041 Mag D 0 10 gph Black Yes 8 0 0 87 D042 Mag D 0 20 gph Red Yes 8 0 0 87 D043 Inv only Mag D None Green Yes 8 0 0 87 Table 9 3 Mag Probe Channel...

Page 85: ...and that polarity required for some sensors is maintained from the sensor to the console If necessary refer to the Sensor Products Application Guide P N 577013 750 for correct sensor console compatib...

Page 86: ...in Coleman fuel for 30 minutes and be allowed to recover in a well ventilated area for up to 7 days DISCRIMINATING SOLID STATE SENSOR OPTICAL P N 794380 343 344 To clean contaminated optical sensors...

Page 87: ...ons All applications of CSLD should conform to the following installation guidelines MAXIMUM TANK CAPACITY Single tank 30 000 gallons Manifolded tanks 30 000 gallons per manifolded set 3 tanks maximum...

Page 88: ...iagram IDLE Evaluate Activity TLS SAMPLE READY Yes IDLE TRUE Yes Test In Progress Yes No Test In Progress No Start Test Test Duration 3 Hours End Test Evaluate Test Test Acceptable No Yes Add Test to...

Page 89: ...5 minutes duration Minimum test time 15 minutes Feedback time dynamic variable of 0 45 minutes duration All probe samples received within this test period are used in the leak analysis Several sample...

Page 90: ...see Figure 11 3 This table contains the last 28 days of leak tests or a maximum of 80 of the most recent tests 2 IA5200 CSLD Rate Test see Figure 11 4 This report contains the CSLD summary of the eval...

Page 91: ...fication status at last evaluation 0 Test valid 1 Test rejected duration too short 2 Test rejected start time too close to a delivery 3 Test rejected excessive dispensing prior to test 4 Test rejected...

Page 92: ...ATA COUNT not enough tests available to evaluate There must be at least 2 acceptable tests 6 NO DATA INTERVAL not enough total test time to evaluate 6 hours 7 NO DATA RANGE tests did not range over a...

Page 93: ...9 1224 3 1329 6 1420 9 1535 5 1603 5 1613 2 1680 6 1739 8 1808 6 1842 4 T 3 REGULAR LAST HOUR 229664 7755 0 7960 6 8006 9 8037 9 8049 1 8049 2 8049 3 8049 0 8021 1 4691 9 4716 8 4804 2 4849 0 4966 7 5...

Page 94: ...118 17 29 547 45 52 44 06 39 35 960312103838 21 2118 13 29 547 45 52 44 06 39 35 960312103908 29 2118 21 29 547 45 52 44 06 39 35 960312103938 28 2118 12 29 546 45 53 44 06 39 36 960312104008 28 2118...

Page 95: ...ng At the threads of the two inch pipe coming from the turbine motor The gasket between the turbine motor and mounting flange At any seal which would allow the column of fuel being held in the pump by...

Page 96: ...period has occurred this does not require that a CSLD record get stored in the rate table Frequent or continuous NO CSLD IDLE TIME messages are an indication of a problem Possible reasons for this mes...

Page 97: ...E to the uncompensated value AVLRTE The most likely cause of excessive compensation is bad probe temperature readings 7 Stuck floats Install a collar on the probe shaft to prevent floats from entering...

Page 98: ...te Table You should manually clear the CSLD Rate Table if data known to be inaccurate had been stored in the table and the source of the inaccurate data was subsequently removed e g after making tank...

Page 99: ...ALARM HISTORY 9 Control A I20100 INVENTORY REPORT 10 Control A I20200 DELIVERY REPORT 11 Control A I20600 TANK ALARM HISTORY REPORT 12 Control A I25100 CSLD RESULTS 13 Control A I60900 SET TANK THERM...

Page 100: ...178 0 000 9607021054 1 0 092 70 7 80 2 89 7 0 05 519 4196 25 5 26 2 193 0 000 9607021900 1 0 105 70 9 80 5 89 8 0 07 568 3837 35 0 34 3 212 0 000 9607030105 3 0 069 71 0 80 7 89 8 0 08 616 3580 41 5...

Page 101: ...79 3 86 5 0 02 587 3965 99 0 4 8 205 0 000 9607132344 3 0 054 70 9 79 9 87 5 0 05 638 3110 51 5 24 7 249 0 000 9607140246 2 0 133 70 1 75 1 86 5 0 04 182 5030 128 5 0 1 144 0 000 9607150252 3 0 054 7...

Page 102: ...easons CSLD is favoring these tests All the tests with status code 1 were rejected due to short intervals DSPNS The dispense factor is an indication of the amount of dispensing that occurred during th...

Page 103: ...analysis DIAGNOSTICS I20100 STATION HEADER INFO MAY 21 2000 10 29 AM TANK PRODUCT VOLUME TLC VOLUME ULLAGE HEIGHT WATER TEMP 1 REGULAR 2311 2303 3705 39 21 0 0 65 2 2 REGULAR SLAVE 3276 3266 4746 41...

Page 104: ...75 1 0 05 944 8567 16 0 14 3 462 0 000 9608040649 1 0 144 72 6 73 7 75 1 0 07 842 8514 21 0 16 6 465 0 000 9608050051 0 0 228 72 3 73 4 75 2 0 07 531 6661 81 5 34 7 541 0 000 9608050309 1 0 030 72 2 7...

Page 105: ...e problem in this example was that the pump wiring to the line leak devices was correct but the line leak tank assignments were incorrect Solution Reassign Tanks 4 and 1 to their installed line leak d...

Page 106: ...GNOSTICS RATE TABLE T 3 REGULAR TIME ST LRT AVTMP TPTMP BDTMP TMRT DSPNS VOL INTVL DEL ULLG THPT RATE TABLE EMPTY IA5300 IA5300 MAR 12 1996 1 54 PM CSLD DIAGNOSTICS VOLUME TABLE T 2 REGULAR LAST HOUR...

Page 107: ...960624141631 31 6526 88 53 302 77 74 79 20 84 17 960624141701 31 6527 34 53 304 77 72 79 17 84 07 960624141731 31 6527 60 53 306 77 73 79 17 83 97 960624141801 31 6527 49 53 308 77 81 79 27 83 89 9606...

Page 108: ...LEADED PLUS PER JUN 26 1996 PASS 3 SUPER UNLEADED PER JUN 26 1996 PASS 4 KEROSENE PER JUN 26 1996 PASS 5 DIESEL PER JUN 26 1996 PASS I20100 STATION HEADER INFO JUN 26 1996 2 36 PM TANK PRODUCT VOLUME...

Page 109: ...9606130608 0 0 324 72 9 73 3 74 8 0 12 763 8464 16 0 7 3 324 0 000 9606170258 0 0 254 73 1 75 4 80 0 0 12 1511 4677 21 5 38 7 484 0 000 9606170334 0 0 424 73 0 75 5 80 2 0 16 1373 4672 112 0 39 3 484...

Page 110: ...during the test ANALYSIS OF THERMAL EXPANSION COEFFICIENT REPORT I60900 Checking the thermal temperature coefficient of expansion value for the tanks reveals that these values were programmed incorre...

Page 111: ...RTE VOL C1 C3 FDBK ACPT THPUT DFMUL RJT 1 9806170430 0 492 14 7 2 0 504 6123 26 20 0 0 0 0 7 13 0 61 0 2 9806170254 0 025 14 8 1 0 015 6238 22 19 0 0 0 0 6 89 0 67 9 3 9806170557 0 033 22 3 1 0 025 62...

Page 112: ...0 02 1620 4335 47 5 30 7 417 7 0 9806060245 0 0 008 63 4 67 7 71 7 0 02 1555 4333 58 0 31 7 417 6 7 9806060527 0 0 420 63 3 67 4 71 2 0 01 1452 4299 16 5 34 4 419 6 4 9806070032 2 0 061 60 9 66 0 71 3...

Page 113: ...71 48 376 63 53 66 18 71 44 980617082537 22 5288 92 48 370 63 52 66 20 71 44 980617082607 12 5287 66 48 361 63 52 66 19 71 44 980617082637 24 5286 69 48 354 63 52 66 19 71 44 980617082707 23 5285 51 4...

Page 114: ...22 5332 77 48 701 63 86 67 12 72 68 980617082507 23 5329 52 48 677 63 85 67 15 72 68 980617082537 22 5324 32 48 639 63 85 67 16 72 68 980617082607 12 5321 19 48 616 63 86 67 16 72 68 980617082637 24...

Page 115: ...STICS RATE TEST TK DATE LRATE INTVL ST AVLRTE VOL C1 C3 FDBK ACPT THPUT DFMUL RJT 1 7001010000 0 000 0 0 5 0 000 0 0 0 0 0 0 0 0 00 0 80 0 2 7001010000 0 000 0 0 5 0 000 0 0 0 0 0 0 0 0 00 0 80 0 3 70...

Page 116: ...ing This caused a gap between probe readings which cleared the volume table CSLD does not perform any tests until the volume table is full 24 hours Solution Keep power turned On to the console CSLD PR...

Page 117: ...RATE TABLE T 1 REGULAR TIME ST LRT AVTMP TPTMP BDTMP TMRT DSPNS VOL INTVL DEL ULLG THPT 9805230026 3 0 050 69 2 14 7 71 3 0 02 2052 2976 24 5 34 7 452 8 2 9805230102 3 0 011 69 2 14 7 71 3 0 03 1991 2...

Page 118: ...8061 43 0 5 2 225 7 8 9806030030 3 0 026 46 5 14 7 71 0 0 01 1487 5697 108 5 25 0 338 7 9 9806030231 1 0 028 46 6 14 7 71 0 0 02 1487 5688 18 5 27 0 339 7 9 9806030308 0 0 014 46 7 14 7 70 9 0 02 1454...

Page 119: ...CSLD PROBLEM 9 TANK 1 FAIL Diagnostics 200 Site ID Site ID Site ID Site ID MAY 18 2000 8 23 TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED 4740 44 69 0 0 61 2 4896 2 PLUS 5740 63 65 0 0 61...

Page 120: ...000 0004280154 3 0 039 58 2 57 6 58 4 0 06 1790 4975 162 5 9 3 369 0 000 0004282311 0 0 061 59 1 57 1 59 4 0 06 1659 6434 129 5 6 4 305 0 000 0004290140 0 0 002 58 9 57 1 59 4 0 06 1464 6434 161 0 9 4...

Page 121: ...7 2 70 3 0 06 1112 5499 140 5 8 7 345 0 000 0005162319 3 0 052 64 1 106 1 69 7 0 14 2548 1734 129 5 29 5 521 0 000 0005170209 3 0 020 63 7 98 6 69 6 0 12 2444 1734 32 0 32 5 521 0 000 0005170352 2 0 0...

Page 122: ...12 IA5100 MAY 7 1999 10 11 AM T 8 REGULAR 1 TIME ST LRT AVTMP TPTMP BDTMP TMRT DSPNS VOL INTVL DEL ULLG THPT 9904120309 0 0 395 64 3 67 8 71 5 0 02 980 8808 36 0 36 8 909 3 0 9904130447 0 0 213 64 8 6...

Page 123: ...LD PROBLEM 11 PERIODIC TEST FAIL TANK 2 Diagnostics 200 Site ID Site ID Site ID NOV 16 1999 1 06 PM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 REGULAR 8543 61 99 0 0 77 4 3139 2 PLUS 3705 32 53...

Page 124: ...emperatures in Tank 2 are abnormally higher than in the other tanks This problem was traced to a stuck relay The pump was running continuously and heating up the fuel Solution Replace the stuck relay...

Page 125: ...981120074112 30 3433 60 36 399 61 85 60 83 57 33 981120074142 30 3433 60 36 399 61 85 60 84 57 33 981120074212 31 3433 57 36 398 61 85 60 84 57 33 981120074242 30 3433 55 36 398 61 85 60 84 57 33 9811...

Page 126: ...42 981120080312 30 3433 05 36 396 61 85 60 89 57 42 981120080342 31 3433 04 36 396 61 85 60 89 57 42 981120080412 30 3433 10 36 396 61 85 60 89 57 41 981120080442 31 3433 07 36 396 61 85 60 89 57 41 9...

Page 127: ...For technical support sales or other assistance please visit www veeder com...

Reviews: