11
CSLD Troubleshooting
Actual CSLD Test Problems Analyzed
11-22
Analysis
The moving average table shows erratic probe readings. Fluid is rising and falling by several gallons.
Solution
Replace probe.
CSLD PROBLEM 5 - TANK 1 IS FAILING
Reports I251, I201, IA52, IA51, and I609 were collected for analysis.
Diagnostics
I25100
JUN 26, 1996 2:37
STATION
HEADER
INFO
PHONE
CSLD TEST RESULTS
TANK
PRODUCT
RESULT
1
UNLEADED
PER: JUN 24, 1996 FAIL
2
UNLEADED PLUS
PER: JUN 26, 1996 PASS
3
SUPER UNLEADED
PER: JUN 26, 1996 PASS
4
KEROSENE
PER: JUN 26, 1996 PASS
5
DIESEL
PER: JUN 26, 1996 PASS
I20100
STATION HEADER INFO
JUN 26, 1996 2:36 PM
TANK
PRODUCT
VOLUME
TLC VOLUME
ULLAGE
HEIGHT
WATER
TEMP
1
UNLEADED
8627
8617
3000
63.42
0.0
76.9
2
UNLEADED PLUS
9286
9278
2341
67.92
0.0
72.2
3
SUPER UNLEADED
8315
8309
3312
61.38
0.0
70.6
4
KEROSENE
5399
5395
598
60.21
0.0
70.9
5
DIESEL
2989
2987
2940
46.27
0.0
70.1
IA5200
JUN 26, 1996 2:37 PM
CSLD DIAGNOSTICS: RATE TEST
TK
DATE
LRATE
INTVL
ST
AVLRTE
VOL
C1
C3
FDBK
ACPT
THPUT
EVAP
RJT
1
9606240446
-0.270
10.3
2 -0.217
6406
21
20
0.0
0.0
44.32
0.000
1