5-8
5
Warning and Alarm Messages
Displayed Alarm Messages
Table 5-9. Relay Alarms
Alarm
Cause
Action
Out Alarm
Console has lost communication with
the relay.
Call for service following the proce-
dures established for your site.
Setup Data Warning
Device setup data problem.
Recheck device setup parameters.
Table 5-10. Pressure Line Leak Alarms
Alarm
Cause
Action
Annual Test Fail Alarm
0.1 gph (0.38 lph) line test failure. Dis-
pensing halts, if programmed to do so.
Consult PLLD Alarm Quick Help Guide and
PLLD diagnostic screens.
Annual Test Needed
Alarm
System failed to perform an annual test
(0.1 gph [0.38 lph]) in the programmed
number of days.
Schedule a 0.1 gph (0.38 lph) test.
Annual Test Needed
Warning
System failed to perform an annual test
(0.1 gph [0.38 lph]) in the programmed
number of days.
Schedule a 0.1 gph (0.38 lph) test.
Continuous Handle On
Alarm
Handle signal has been active for a pro-
grammed number of hours.
Call for service following the procedures
established for your site.
Fuel Out Alarm
Tank product level below 10-inch (25.4 cm)
level - cannot pump when active.
Schedule a delivery.
Gross Test Fail Alarm
3 gph (11.3 lph) line test failure. Dispens-
ing halts, if programmed to do so, while the
alarm is active.
Consult PLLD Alarm Quick Help Guide and
PLLD diagnostic screens.
Line Equipment Alarm
A problem with the pressure measurement
equipment has been detected.
Call for service following the procedures
established for your site.
Low Pressure Alarm
Low pump dispense pressure is detected
during a dispense. Dispensing halts if pro-
grammed to do so.
The next handle up will restart the pump.
Periodic Test Fail Alarm
0.2 gph (0.76 lph) test failure. Dispensing
halts, if programmed to do so.
Consult PLLD Alarm Quick Help Guide and
PLLD diagnostic screens.
Periodic Test Needed
Alarm
A periodic in-tank leak (0.2 gph [0.76 lph])
test has not been successfully completed
within the programmed number of days.
Schedule a 0.2 gph (0.76 lph) test.
Periodic Test Needed
Warning
A periodic in-tank leak (0.2 gph [0.76 lph])
test has not been successfully completed
within the programmed number of days.
Schedule a 0.2 gph (0.76 lph) test.
Setup Data Warning
The default line length was not changed to
reflect the actual line length.
Enter the correct line length(s).
Sensor Open Alarm
Pressure sensor reading is less than -8 psi
(-51.2 kPa). Only tested while the pump is
running. Dispensing halts if programmed
to do so.
3 gph (11.3 lph) test must pass to clear the
alarm. Call for service following the proce-
dures established for your site.