PROBA 5
Doc.nr: 190356
Version: 1.0
6.1.5 Heating settings
No.
Description
range
units
default
1401
Differential heating
0.1..15.0
K
0.5
1402
Offset heating
-25.0..25.0
K
0
1410
P band heating
0.1..30.0
K
5.0
1411
I time heating
0..999
Min.
0
1412
D action heating
0..100
-
0
1413
Offset PID heating
-25.0..25.0
K
0
1432
Heating off at absolute maximum alarm 1 in the zone
0..1
-
1
1450
Heating off at
0..3
-
0
0 = never
1 = door open
2 = blocking
3 = both
6.1.6 Gassing settings
No.
Description
range
units
default
1501
Differential gas concentration
1..500
ppm
250
1502
Offset gas concentration
-300..300
ppm
0
1503
Door lock gas concentration
0..2000
ppm
100
1504
Allow end of gas period with ventilation
0..1
-
0
1505
Gas sensor only for information
0..1
-
0
1510
Gas pulse pause at time gassing
0..1
-
0
1511
Pulse time gassing
0..999
min
0
1512
Pause time gassing
0..999
min
0
1520
Maximal gas inlet time during controlling on concentration
0.9999
min
40
1521
Gas minimal/maximal pulse time active during gassing on concentration
0..1
-
0
1525
Stop gassing when maximum inlet time reached
0..1
-
0
1526
Gas concentration zero if below
0..200
ppm
0
1527
Gas concentration zero delay
0..999
min
0