INSTALLATION

 

INSTRUCTIONS

 

OPTION

 

952

 

:

 

Thermostat

 

Kronos

 

GA11

 

 

 

DESCRIPTION

 

The Kronos GA11 is a weekly programming digital chronothermostat 
used for the remote control of  the ULSA gas‐fired air heaters. 

 

ATTENTION :  Before  turning  on,  check  the  cables  (incorrect  wiring 
may damage the thermostat and compromise safety. 

Connect and disconnect the control sytem only in absence of voltage.  
Avoid exposing to dripping water. 

 

 
 

GENERAL

 

FEATURES

 

 

 

Graphic LCD display (128x64 px) 

 

Backlight timer 20 seconds 

 

LED for diagnostics/signaling 

 

7 variabele function keys 

 

Weekly programming 

 

4  temperature  levels  (T0,  T1,  T2  & 

T3) 

 

Resolution (0.5°C temperature set) 

 

Resolution (0.1°C temperature read) 

 

Minimum  interval  programming : 

15’‘ 

 

SELV  insulation  (Safety  Extra  Low 
Voltage) 

 

Bi‐polar connection, non‐polarized 

 

 

TECHNICAL

 

DATA

 

 

Operating temperature :  0°C +50°C 

 

Humidity : 95% maximum at 40°C 

 

Power sypply : low voltage (3V) (via communication with control board of the air heater) 

 

Protection degree : IP30 

 

Dimensions : 140x90x32mm 

 

Compliance : directive 2004/108/CE (EMC) / directive 2006/95/CE (LVD) 

 

 

INSTRUCTIONS

 

FOR

 

USE

 

The buttons have any versatile utilization depending on the selected menu. The use of buttons is facilitated by the 

indications with text, icons and other graphics that appear on the display. 
 

The vertical buttons on the left : used to navigate the setup menu or to select the parameters 

The vertical buttons on the right : used to vary temperature and function increase/decrease (+/‐) 
The horizontal buttons at the bottom : used to confirm or cancel the settings or to enter/exit the submenus 

The center button : used for special functions (e.g. unlock heater) 
 

Under the center button there is a LED giving following information : 

 

Continuous red LED : error or no communication with the heater 

 

Intermittent red LED : lockout heater 

 

Intermittent yellow LED :  anomaly 

 

Continuous green LED : chronothermostat is resuming work after power failure 

 

®

Figure 1

Summary of Contents for Kronos GA11

Page 1: ...imum at 40 C Power sypply low voltage 3V via communication with control board of the air heater Protection degree IP30 Dimensions 140x90x32mm Compliance directive 2004 108 CE EMC directive 2006 95 CE LVD INSTRUCTIONS FOR USE The buttons have any versatile utilization depending on the selected menu The use of buttons is facilitated by the indications with text icons and other graphics that appear o...

Page 2: ...e function of the active thermoregulation automatic manual summer or standby Automatic Temperature control environment according to the weekly program set by the user Program seen as a graph of the current day Manual Temperature control environment in accordance with user selected temperature thermostat function Summer Temperature control environment disable Summer ventilation can be activated man...

Page 3: ...ng the button again the standby menu appears The standby mode allows you to turn off the system temperature control environment ventilation are disabled The first level menu is circular meaning that all screens are accessible by pushing the OVERTIME MODE Continuing and pushing the button again you can choose to activate the operating mode Overtime In operating mode Overtime the room thermoregul at...

Page 4: ...ormation AUTOMATIC MODE By pressing the button again you return to the first option In case the automatic mode is already active it does noet matter whether you push NO or OK SETTING MENU Programming This submenu allows you to manage temperature control environment weekly program time setting and language choice Selecting the option Programming you enter the weekly program submenu Choosing the opt...

Page 5: ... method used by the chrono thermostat for controlling room temperature This menu allows you to set the differential which can vary between 0 2 º C and 5 0 º C default value 2 0 º C d is the thermal differential Max is the maximum rate Ti and Ta stand for respectively room temperature set and room temperature measured The required percentage P is calculated as follows if Ta Ti d then P Max if Ti d ...

Page 6: ...the function of reading and writing of TSP To change a TSP you must select the index idx desired using the and keys and push the SET button After that following screen appears where you can enter with the and buttons the desired value In the event that the board does not include the writing of this TSP read only the changes made to it will have no effect The number of TSP depends on the control bo...

Page 7: ... Read slave The last item Read Slave of the PARAMETERS MENU you can view the percentage the value of the respective temperature probe of power and the LC1 temperature of hot air generators You are shown a number of rows corresponding to the number of slaves connected up to a maximum of 10 slaves In addition pushing from the main screen simultaneously the buttons 5 and 6 shown below in any operatin...

Page 8: ...heir charging status WARNINGS ABOUT THE BACKLIGHT The display backlight is obtained from the reserve described in the previous paragraph It is possible therefore that in case of newly connected chronothermostat the brightness is minimal or absent because of insufficient internal charge this must not alarm as they are just a few hours of connection because the backlight to begin to be efficient You...

Page 9: ...e of temp 0 C eg value 20 pas de ven l value 20 C vent P05 Offset_EF_MAX 0 50 0 To reduce maximum speed venter motor factory setting Example Max speed 7200 RPM P05 25 Max speed 7200 1 0 25 5400 RPM P06 Offset_EF_MIN 0 200 0 To increase minimum speed venter motor factory setting Example Min speed 1350 RPM P06 50 Min speed 1350 1 0 5 2025 RPM P07 0 10V threshold 0 5 5 0 1 0 V Setting threshold value...

Page 10: ...working even when it is in off state wiring problem J11 signal 2 3 4 5 J11 signal 4 is broken bad print can be bad venter motor venter can also be in thermal lockout wait 1hour and try again 27 SR opened or not connected forced purge LC1 open or not connected 60 Parasite flame forced purge Sperious flame at start up you don t get lockout only if this stays for 10s this will change to error 15 81 I...

Page 11: ...by GA11 Option 4 no additional setting required 1 GA11 for 4 units unit 1 no additional sensor unit 2 additional sensor unit 3 no additional sensor unit 4 no additional sensor unit 1 control through set point room temperature by GA11 unit 2 control through set point GA11 and room temperature SA temperature sensor unit 3 control through set point room temperature by GA11 unit 4 control through set ...

Page 12: ...A temperature sensor unit 3 controlled through setpoint GA11 and room temperature SA temperature sensor unit 4 controlled through setpoint GA11 and room temperature SA temperature sensor Example Setpoint GA11 25 C Room temperature GA11 24 C is van geen belang SA unit 1 23 C SA unit 2 25 C SA unit 3 23 5 SA unit 4 22 C diff 2 C unit 1 is working at 100 unit 2 is working at 0 unit 3 is working at 75...

Reviews: