17040952—ENG 

 

2/12 

Starting... 

Thermostat is in the process of connection to the heater 

Ambient probe error  Room temperature sensor thermostat damaged 

Fault code XXX 

There is an anomaly or a lockout on the heaters – code XXX 

Comm. error 

There is a communication error between thermostat and heater 

Error ID XX 

Faulty interpretation of information sent by heater to the thermostat 

 

 

The most frequently used functions by the user are available in the main menu. It is possible to quickly browse 
through the pages. 

 
The first time or after a reset, the 

language

 

menu

 appears on the display.   

By pushing OK you confirm the selection.   

Through the SETTING MENU this choice can still be changed later. 
 

 
Then the 

current

 

time

 can be entered. 

The buttons on the left allow you to select the menu – the buttons on the 

right allow you to change the values.  
Push the OK button to validate. The ESC button allows you to continue 

without making changes to the time settings. 

 

 
 

MAIN

 

SCREEN

 

Following items are shown on the main screen : 

 

the day of the week (intermittent if not updated) 

 

the current time (intermittent if not updated) 

 

the temperature measured (measurement every 10sec) 

 

an icon indicating the function of  the active thermoregulation 

(automatic, manual, summer or standby)  

 

 

Automatic 

Temperature control environment 
according to the weekly program 

set by the user. Program seen as a 
graph of the current day. 

 

Manual

Temperature control environment in 
accordance with user‐selected temperature 

(thermostat function) 

 

Summer 

Temperature control environment 

disable. Summer ventilation can be 
activated manually. 

 

Standby

Temperature control environment disable.

(no frost protection) 

 

In automatic mode, the chronothermostat performs the temperature control program as set for the current day. The 
graph is visible at the bottom of the display.The graph is divided into time intervals of 15 minutes, corresponding to a 

pixel horizontally and appearing in the four programmable temperature levels. 

 
Near the icon of the operation mode, other icons may appear, meaning following. 

 

Indicates that heater is turned on (the size of the symbol depends on the modulation level of the flame

 

Lockout of the heater

 

Fault 

Connection icon symbol  (if no icon appears)

(P.S : if heater is in standby mode and has no problem, no icon will appear)

 

 
In addition, under  

the room temperature  

indication, a text may  
be shown providing  

some information as  
shown next 

 

 

Remark : please consult the thermoregulation documentation for detailed description of the fault codes.  

ITALIANO 
FRANCAIS 
ENGLISH 
NEDERLANDS 
DEUTSCH 

Summary of Contents for Kronos GA11

Page 1: ...imum at 40 C Power sypply low voltage 3V via communication with control board of the air heater Protection degree IP30 Dimensions 140x90x32mm Compliance directive 2004 108 CE EMC directive 2006 95 CE LVD INSTRUCTIONS FOR USE The buttons have any versatile utilization depending on the selected menu The use of buttons is facilitated by the indications with text icons and other graphics that appear o...

Page 2: ...e function of the active thermoregulation automatic manual summer or standby Automatic Temperature control environment according to the weekly program set by the user Program seen as a graph of the current day Manual Temperature control environment in accordance with user selected temperature thermostat function Summer Temperature control environment disable Summer ventilation can be activated man...

Page 3: ...ng the button again the standby menu appears The standby mode allows you to turn off the system temperature control environment ventilation are disabled The first level menu is circular meaning that all screens are accessible by pushing the OVERTIME MODE Continuing and pushing the button again you can choose to activate the operating mode Overtime In operating mode Overtime the room thermoregul at...

Page 4: ...ormation AUTOMATIC MODE By pressing the button again you return to the first option In case the automatic mode is already active it does noet matter whether you push NO or OK SETTING MENU Programming This submenu allows you to manage temperature control environment weekly program time setting and language choice Selecting the option Programming you enter the weekly program submenu Choosing the opt...

Page 5: ... method used by the chrono thermostat for controlling room temperature This menu allows you to set the differential which can vary between 0 2 º C and 5 0 º C default value 2 0 º C d is the thermal differential Max is the maximum rate Ti and Ta stand for respectively room temperature set and room temperature measured The required percentage P is calculated as follows if Ta Ti d then P Max if Ti d ...

Page 6: ...the function of reading and writing of TSP To change a TSP you must select the index idx desired using the and keys and push the SET button After that following screen appears where you can enter with the and buttons the desired value In the event that the board does not include the writing of this TSP read only the changes made to it will have no effect The number of TSP depends on the control bo...

Page 7: ... Read slave The last item Read Slave of the PARAMETERS MENU you can view the percentage the value of the respective temperature probe of power and the LC1 temperature of hot air generators You are shown a number of rows corresponding to the number of slaves connected up to a maximum of 10 slaves In addition pushing from the main screen simultaneously the buttons 5 and 6 shown below in any operatin...

Page 8: ...heir charging status WARNINGS ABOUT THE BACKLIGHT The display backlight is obtained from the reserve described in the previous paragraph It is possible therefore that in case of newly connected chronothermostat the brightness is minimal or absent because of insufficient internal charge this must not alarm as they are just a few hours of connection because the backlight to begin to be efficient You...

Page 9: ...e of temp 0 C eg value 20 pas de ven l value 20 C vent P05 Offset_EF_MAX 0 50 0 To reduce maximum speed venter motor factory setting Example Max speed 7200 RPM P05 25 Max speed 7200 1 0 25 5400 RPM P06 Offset_EF_MIN 0 200 0 To increase minimum speed venter motor factory setting Example Min speed 1350 RPM P06 50 Min speed 1350 1 0 5 2025 RPM P07 0 10V threshold 0 5 5 0 1 0 V Setting threshold value...

Page 10: ...working even when it is in off state wiring problem J11 signal 2 3 4 5 J11 signal 4 is broken bad print can be bad venter motor venter can also be in thermal lockout wait 1hour and try again 27 SR opened or not connected forced purge LC1 open or not connected 60 Parasite flame forced purge Sperious flame at start up you don t get lockout only if this stays for 10s this will change to error 15 81 I...

Page 11: ...by GA11 Option 4 no additional setting required 1 GA11 for 4 units unit 1 no additional sensor unit 2 additional sensor unit 3 no additional sensor unit 4 no additional sensor unit 1 control through set point room temperature by GA11 unit 2 control through set point GA11 and room temperature SA temperature sensor unit 3 control through set point room temperature by GA11 unit 4 control through set ...

Page 12: ...A temperature sensor unit 3 controlled through setpoint GA11 and room temperature SA temperature sensor unit 4 controlled through setpoint GA11 and room temperature SA temperature sensor Example Setpoint GA11 25 C Room temperature GA11 24 C is van geen belang SA unit 1 23 C SA unit 2 25 C SA unit 3 23 5 SA unit 4 22 C diff 2 C unit 1 is working at 100 unit 2 is working at 0 unit 3 is working at 75...

Reviews: