17040952—ENG
10/12
ERROR
CODES
Description
Solution
001
…
005
007
…
009
6
OpenTherm™
reset
disabled
If
more
than
5
reset
attempts
in
15
minutes
occurs
from
OpenTherm
™
(GA11),
device
can
only
be
unloc
10
Lockout
for
no
ignition
After
5
ignition
attemps
lockout
11
Lockout
for
safety
limit
thermostat
intervention
Lockout
if
LC3
is
open
(ts)
14
Lockout
for
no
air
during
prepurge
(option
Q10,
for
RPM
absence)
Error
fault
PWM
signla
venter
‐
bad
connection
in
cable
between
venter
and
board
(J11
signal
2
‐
3
‐
4
‐
5)
‐
broken
board?
15
Lockout
for
parasite
flame
(option
K10)
After
10s
of
sperious
flame
you
get
error
15
(lockout)
17
Lockout
(this
value
should
occur
after
first
power
‐
on)
101
Lockout
for
wrong
RPM
signal
after
pre
‐
purge
time
If
venter
speed
has
not
reached
te
preset
speed
or
is
to
far
out
of
bounds
19
APS
opened
during
operating
Delta
p
(S3)
is
open
‐‐
>
main
fan
not
running
after
±
100s
after
heat
cycle
20
Unexpected
RPM
signal
on
start
‐
up
Venter
is
working
even
when
it
is
in
off
state
‐
wiring
problem
(J11
signal
2
‐
3
‐
4
‐
5)
‐
J11
signal
4
is
broken
‐‐
>
bad
‐
can
be
bad
venter
motor
(venter
can
also
be
in
thermal
lockout
wait
1hour
and
try
again)
27
SR
opened
or
not
connected
(forced
purge)
LC1
open
or
not
connected
60
Parasite
flame
(forced
purge)
Sperious
flame
at
start
‐
up
you
don't
get
lockout
only
if
this
stays
for
10s
this
will
change
to
error
15
81
Internal
communication
fault
Bad
should
be
returned
to
manufacturer
82
LC1
short
circuit
led
is
orange
(remove
power
supply,
fix
the
lc1,
supply
power
again)
87
Switch
‐
Off
Temperature
Threshold
exceeded
LC1
has
reached
its
setpoint,
error
is
gone
when
temp
is
again
under
this
value
88
Resistor
for
menu
selection
(J19)
not
connected/short
circuited
The
resistor
needs
to
be
placed
on
the
at
first
power
up
This
is
to
choose
the
correct
setup
(led
is
orange)
29
internal
hardware
error
Return
to
manufacturer
22
special
software
"option
q60.hex"
:
code
22
is
no
error
code
but
a
reporting
code
(wait)
indicating
that
venter
motor
is
not
active
and
that
unit
only
will
restart
at
restart
of
ve
Internal
fault
Contact
technical
department