17040952—ENG 

 

8/12 

USE

 

OF

 

BATTERIES/BACKLIGHT

 

 
The chronothermostat is provided with an internal 

energy store which can compensate for a power cut‐off 
for a few hours; in this way the user will not have to set 

the current time, room temperatures and week program 

again. However, the internal energy store consumption 
time varies depending on the room temperature and 

humidity, as well as on the ageing of components. In 
order for the internal energy store to be fully effective, 

the chronothermostat must have been correctly 

energized for a couple of days at least without 
interruption. If frequent and/or long cut‐offs of the 

boiler power supply are expected, it is possible to avoid 

losing chronothermostat data by installing two alkaline 
batteries type AAA LR03 1,5V into the appropriate slot 

on the fixing base. In this way, the additional internal 
energy store, made by new batteries, enables to 

preserve data for a period even longer than one year 

under no power supply conditions. It is advisable not to 
keep batteries inside the chronothermostat for a long 

time during normal operation (power supply presence) 
to prevent any battery liquid leakage from damaging the 

chronothermostat itself. Finally, please note that  

Kronos GA11 does not provide any information about 
the presence of batteries or their charging status.    

WARNINGS

 

ABOUT

 

THE

 

BACKLIGHT

  The display 

backlight is obtained from the reserve described in the 

previous paragraph. It is possible, therefore, that in case 

of newly connected chronothermostat the brightness is 
minimal or absent because of insufficient internal 

charge: this must not alarm as they are just a few hours 
of connection, because the backlight to begin to be 

efficient. You can, if desired, to remedy this temporary 

lack of backlighting installing alkaline batteries, making 
sure the polarity and following the instructions in the 

previous paragraph. 
 

INSTALLATION

 

ON

 

THE

 

WALL

 

 
First step, remove the cover containing the electronic 

board by pushing the appropriate button that says 
"PUSH", located on the lower unit and rotating the cover 

itself up, until it is fully removed, as shown in figure 2. 

For the fixing on the wall it is possible to use many holes 
provided on the bottom of the base, in this case, see 

figure 3. 

Figure 2 

 
 

 
 

 

 
 

 
 

Then is possible to wire the circuit board unit using 

the appropriate terminal, regardless of the polarity 
(the two conductors can be exchanged). It is 

recommended to use a twisted pair cable (example 

H03RR‐F o H03VV‐F) size between 0,5 mm2 and 2,5 
mm2, the length should not exceed 50m (eg : GA11 – 

50m – unit 1 – 50m – unit 2 – 50m – unit 3). The 
resistance of each conductor, in any case, should not 

exceed 5 ẇ. In environments with electromagnetic 

interference it is recommended to use a shielded 
twisted pair cable. 

 
Figure 3 : Fixing holes  

 

 
Figure 4 : External dimensions 

 

 
 

Summary of Contents for Kronos GA11

Page 1: ...imum at 40 C Power sypply low voltage 3V via communication with control board of the air heater Protection degree IP30 Dimensions 140x90x32mm Compliance directive 2004 108 CE EMC directive 2006 95 CE LVD INSTRUCTIONS FOR USE The buttons have any versatile utilization depending on the selected menu The use of buttons is facilitated by the indications with text icons and other graphics that appear o...

Page 2: ...e function of the active thermoregulation automatic manual summer or standby Automatic Temperature control environment according to the weekly program set by the user Program seen as a graph of the current day Manual Temperature control environment in accordance with user selected temperature thermostat function Summer Temperature control environment disable Summer ventilation can be activated man...

Page 3: ...ng the button again the standby menu appears The standby mode allows you to turn off the system temperature control environment ventilation are disabled The first level menu is circular meaning that all screens are accessible by pushing the OVERTIME MODE Continuing and pushing the button again you can choose to activate the operating mode Overtime In operating mode Overtime the room thermoregul at...

Page 4: ...ormation AUTOMATIC MODE By pressing the button again you return to the first option In case the automatic mode is already active it does noet matter whether you push NO or OK SETTING MENU Programming This submenu allows you to manage temperature control environment weekly program time setting and language choice Selecting the option Programming you enter the weekly program submenu Choosing the opt...

Page 5: ... method used by the chrono thermostat for controlling room temperature This menu allows you to set the differential which can vary between 0 2 º C and 5 0 º C default value 2 0 º C d is the thermal differential Max is the maximum rate Ti and Ta stand for respectively room temperature set and room temperature measured The required percentage P is calculated as follows if Ta Ti d then P Max if Ti d ...

Page 6: ...the function of reading and writing of TSP To change a TSP you must select the index idx desired using the and keys and push the SET button After that following screen appears where you can enter with the and buttons the desired value In the event that the board does not include the writing of this TSP read only the changes made to it will have no effect The number of TSP depends on the control bo...

Page 7: ... Read slave The last item Read Slave of the PARAMETERS MENU you can view the percentage the value of the respective temperature probe of power and the LC1 temperature of hot air generators You are shown a number of rows corresponding to the number of slaves connected up to a maximum of 10 slaves In addition pushing from the main screen simultaneously the buttons 5 and 6 shown below in any operatin...

Page 8: ...heir charging status WARNINGS ABOUT THE BACKLIGHT The display backlight is obtained from the reserve described in the previous paragraph It is possible therefore that in case of newly connected chronothermostat the brightness is minimal or absent because of insufficient internal charge this must not alarm as they are just a few hours of connection because the backlight to begin to be efficient You...

Page 9: ...e of temp 0 C eg value 20 pas de ven l value 20 C vent P05 Offset_EF_MAX 0 50 0 To reduce maximum speed venter motor factory setting Example Max speed 7200 RPM P05 25 Max speed 7200 1 0 25 5400 RPM P06 Offset_EF_MIN 0 200 0 To increase minimum speed venter motor factory setting Example Min speed 1350 RPM P06 50 Min speed 1350 1 0 5 2025 RPM P07 0 10V threshold 0 5 5 0 1 0 V Setting threshold value...

Page 10: ...working even when it is in off state wiring problem J11 signal 2 3 4 5 J11 signal 4 is broken bad print can be bad venter motor venter can also be in thermal lockout wait 1hour and try again 27 SR opened or not connected forced purge LC1 open or not connected 60 Parasite flame forced purge Sperious flame at start up you don t get lockout only if this stays for 10s this will change to error 15 81 I...

Page 11: ...by GA11 Option 4 no additional setting required 1 GA11 for 4 units unit 1 no additional sensor unit 2 additional sensor unit 3 no additional sensor unit 4 no additional sensor unit 1 control through set point room temperature by GA11 unit 2 control through set point GA11 and room temperature SA temperature sensor unit 3 control through set point room temperature by GA11 unit 4 control through set ...

Page 12: ...A temperature sensor unit 3 controlled through setpoint GA11 and room temperature SA temperature sensor unit 4 controlled through setpoint GA11 and room temperature SA temperature sensor Example Setpoint GA11 25 C Room temperature GA11 24 C is van geen belang SA unit 1 23 C SA unit 2 25 C SA unit 3 23 5 SA unit 4 22 C diff 2 C unit 1 is working at 100 unit 2 is working at 0 unit 3 is working at 75...

Reviews: