PROBA 5
Doc.nr: 190356
Version: 1.0
Page
50
6.1.7 Ventilation settings
No.
Description
range
units
default
1601
Ventilate at maximal ethylene level
0..1
-
0
1602
Ventilate during gassing if maximal ethylene level has reached
0..1
-
0
1603
Maximal ethylene level
0..2000
ppm
2000
1604
Differential maximal ethylene level
0..1000
ppm
500
1610
Ventilate at maximal CO2 level
0..1
-
0
1611
Ventilate during gassing if maximal CO2 level has reached
0..1
-
0
1612
Maximal CO2 level
0..3000
ppm
3000
1613
Differential maximal CO2 level
0..1000
ppm
500
6.1.8 Humidity control settings
No.
Description
range
units
default
1701
Differential humidifying
1..50
%RH
3
1702
Differential dehumidifying
1..50
%RH
3
1703
Offset humidity control
-25..25
%RH
0
1710
Humidity control off at
0..3
-
0
0 = never
1 = door open
2 = blocking
3 = both
1720
RH alarm active
0..1
-
0
1721
Maximum RH alarm
0..100
%RH
100
1722
Minimum RH alarm
0..100
%RH
0
1723
Differential RH alarms
1..50
%RH
3
1724
RH alarm off if door is open
0..1
-
0
1725
Delay minimum RH alarm
0..999
min
0
1726
Delay maximum RH alarm
0..999
min
0