6.3.2 Other sensors settings
No.
Description
range
units
default
3131
Read out C2H4 per
0..3
-
0
3132
Value at 0 mA (0V)
-9999..9999
-
0
3133
Value at 4 mA (2V)
-9999..9999
-
0
3134
Value at 8 mA (4V)
-9999..9999
-
63
3135
Value at 12 mA (6V)
-9999..9999
-
125
3136
Value at 16 mA (8V)
-9999..9999
-
188
3137
Value at 20 mA (10V)
-9999..9999
-
250
3138
Offset C2H4 sensor
-1000..1000
-
0
3141
Read out CO2 per
0..3
-
0
3142
Value at 0 mA (0V)
-9999..9999
-
0
3143
Value at 4 mA (2V)
-9999..9999
-
0
3144
Value at 8 mA (4V)
-9999..9999
-
0
3145
Value at 12 mA (6V)
-9999..9999
-
0
3146
Value at 16 mA (8V)
-9999..9999
-
0
3147
Value at 20 mA (10V)
-9999..9999
-
0
3148
Offset CO2 sensor
-1000..1000
-
0
3149
MODBUS address CO2 sensor
0..99
-
0
3151
Read out O2 per
0..3
-
0
3152
Value at 0 mA (0V)
-9999..9999
-
0
3153
Value at 4 mA (2V)
-9999..9999
-
0
3154
Value at 8 mA (4V)
-9999..9999
-
0
3155
Value at 12 mA (6V)
-9999..9999
-
0
3156
Value at 16 mA (8V)
-9999..9999
-
0
3157
Value at 20 mA (10V)
-9999..9999
-
0
3158
Offset O2 sensor
-1000..1000
-
0
3161
Read out RH per
0..3
-
0
3162
Value at 0 mA (0V)
-9999..9999
-
0
3163
Value at 4 mA (2V)
-9999..9999
-
0
3164
Value at 8 mA (4V)
-9999..9999
-
0
3165
Value at 12 mA (6V)
-9999..9999
-
0
3166
Value at 16 mA (8V)
-9999..9999
-
0
3167
Value at 20 mA (10V)
-9999..9999
-
0
3168
Offset RH sensor
-1000..1000
-
0
3171
CO2 sensor source
0..2
3172
O2 sensor source
0..2
6.4 Parameters output
6.4.1 Adjusting analogue output
No.
Description
range
units
default
3210
0V out at temperature
-10.0..+40.0
°C
-10.0
3211
10V out at temperature
-10.0..+40.0
°C
+40.0