4.2.10.
Top vent connection, vertical vent rise with
horizontal rear termination (Fig.13)
Manufactured by Miles Industries Ltd., British Columbia, Canada
10
Can be used with either #551DVK standard vent kit or #984
Dura-vent terminal cap and accessories.
Adapter #817VAK, one 90° vent elbow #990B and Dura-vent
pipe lengths will be required.
(See venting options section of this manual).
No more than two 90°elbows must be used.
The location requirements are (See figure 13):-
Minimum Maximum
A
: From floor to top of
vent duct
4ft
(122cm)
11ft
(335cm)
B
: Back of appliance
to inside wall
3
1
/
4
in
(79mm)
-
C
: Vertical pipe run
9in
(23cm)
8ft
(244cm)
D
: Horizontal pipe run
- 4ft
6in
(137cm)
E
: Clearance to
combustible materials
above horizontal pipe
run
2
5
/
8
in
(6.7cm)
-
F
: Clearance to
combustible materials
below horizontal pipe
run
1
5
/
16
in
(3.3cm)
-
G
: Clearance to
combustible materials
all round vertical pipe
run and at sides of
horizontal pipe run
1
5
/
16
in
(3.3cm)
-
Figure 13
4.2.11.
Top vent connection, vertical vent
rise with horizontal side
termination (Figs.13 &14)
Figure 14
Can be used with either #551DVK standard vent
kit or #984 Dura-vent terminal cap and
accessories.
Adapter #817VAK, one 90° vent elbow #990B
and Dura-vent pipe lengths will be required.
(See venting options section of this manual).
No more than two 90°elbows must be used.
All vertical dimension, pipe run and clearance
limits are as section 4.2.10.
The minimum floor location is shown in figure
14.
4.2.12.
Top vent connection, vertical vent
rise with horizontal side or rear
snorkel termination
The dimensional requirements in sections 4.2.10
and 4.2.11 apply.
Adapter #817VAK, one 90° vent elbow #990B, Dura-vent pipe lengths and a Dura-vent snorkel termination will be required.
#942 Dura-vent thimble kit may also be necessary.
(See venting section of this manual).