Section 14 - Troubleshooting
MC032 - MCP-25 Control
Problem
Possible Cause
Possible Solution
5. The glue
pattern length
is correct, but
the pattern is
not in the
correct
position.
5a. Cell-to-gun setting is
incorrect (glue-pattern-
edit menu).
5b. Pattern-delay settings are
incorrect (glue- pattern-
edit menu).
5c. Valve’s turnon and/or
turnoff times are incorrect
(setup menu).
5d. Nozzle is too far from
product.
5e. Scanner assignments are
incorrect.
5f. Scanner lockout value is
too small.
5g. Ratio compensation is
incorrect.
5a. Enter proper cell-to-gun setting (glue-pattern-
edit menu).
5b. Enter proper pattern-delay settings.
5c. Enter proper turnon and turnoff times for the
valves (setup menu).
5d. Adjust the valve so that the nozzle is closer
to the product.
5e. Assign proper scanner to the valve(s).
5f. Increase the scanner lockout value (glue-
pattern-edit menu).
5g. Enter proper ratio compensation (setup
menu).
6. Length and
position of the
glue pattern
are not
correct.
6a. Ratio compensation is
incorrect.
6b. Correction factor is
incorrect.
6c. Incorrect glue mode is
selected.
6d. Incorrect repeat factor is
entered.
6e. Incorrect unit of measure
is being used.
6f. Scanner assignments are
incorrect.
6g. Incorrect encoder is
assigned to valve(s).
6h. Incorrect “Ton” and “Toff”
values have been
entered.
6a. Enter proper ratio compensation (setup
menu).
6b. Ensure that the correction factor (setup
menu) is correct.
6c. Select the correct glue mode (glue-pattern-
edit menu).
6d. Ensure that the repeat factor is correct (glue-
pattern-edit menu).
6e. Ensure that the proper measuring units
(either metric or imperial) have been entered
for the glue patterns.
6f. Ensure that the scanner assignment to the
valves is correct (glue-pattern-edit menu).
6g. Ensure that the encoder assignment is
correct (setup menu).
6h. Ensure that the “Ton” and “Toff” values are
correct (setup menu).