geoTHERM exclusive VWS 0020051614_00 installation instructions
Display shown
Description
Factory setting
Auxiliary heater
C7
Aux on during CH
no CH
Aux on during DHW
comfort
CH start at
-600°min
>Settable values
Aux on during CH
no CH:
CH blocked.
comfort:
CH enabled, dependent on Out T. aux htr
on and °mins lag/gain.
CH only:
Heating mode by means of auxiliary heat-
ing only, e.g. in emergency operation
Aux on during DHW
no CH:
CH blocked
comfort:
Auxiliary heating supplies the temperature
level that the compressor cannot provide
(approx. > 58 °C cylinder temperature)
CH only:
DHW heating by means of auxiliary heating
only, e.g. in emergency operation (if "no CH" was
previously activated, a max. DHW temp. of approx.
58 °C applies; if "CH" was activated, the max. DHW
temp set in C6 applies
CH start at:
Setting the degree minutes until the
auxiliary heating starts, added to the degree minutes
for compressor start.
Example: -600°min plus -120°min
=> start at -720°min.
Out T. aux htr on: The auxiliary heating is only ena-
bled for post-heating in heating mode below this
temperature (can be set in Menu A3).
no CH
no CH
Cooling
C8
Max Flow Setpoint.
22°C
>Select
Flow temperature:
Display of target flow tempera-
ture The value can be changed.
20°C
Legionella protect
C9
Parameters
Legionella protect
Off
Legionella start
04:00
>Select
Legionella protect:
OFF/Mo/Tu/We/Th/Fr/Sa/Su
Start legionellas:
The preset time of day determines
when the anti-Legionella function will start.
The anti-Legionella function is carried out by the
auxiliary heating on the preset day of the week, at
the preset time, if the auxiliary heating has been ac-
tivated.
For this purpose, the controller sets the flow set-
point to 76 °C/74 °C (2K hysteresis). The anti-Le-
gionella function is terminated when the current
flow temperature at the cylinder has reached 73 °C
for a duration of at least 30 min, or after 90 minutes
if 73 °C is not reached (e.g., if hot water is drawn
during this period).
Off
04:00
Table 8.4 Parameters that can be set in the Code level (cont.)
Controller 8