7
vacon • 68
Technical data
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Communication
interface
Fieldbus
Standard: Serial communication (RS485/
Modbus);
Optional: CANopen; Profibus DP, Lonworks,
DeviceNet, Profinet IO, Ethernet IP, Modbus
TCP, EtherCAT, AS-interface
Status indicators
Drive status indicators (LED) on top side
(POWER, RUN, FAULT, READY)
Ambient conditions
Ambient operating
temperature
-10°C…+40°C
Extended temperature
range
up to 50°C with current derating (see chapter
1.8)
Storage temperature
-40°C…+70°C
Relative humidity
0 to 100% R
H
. Good resistance to most acids,
alkalis and oils. Contact factory for more
details.
Pollution degree
PD2 used for PCB design.
However the drive is suitable for outdoor use
because of dust-tight enclosure to numeral 6
[acc. to IEC 60529]
Altitude
100% load capacity (no derating) up to
1,000m;
derating 1% / 100m at 1.000...3.000m
Degree of protection
IP66/Type 4X (IP65 when used with Simple
Operator Panel +QDSH)
Stationary vibration:
Sinusoidal
3 Hz
≤
f
≤
8.43 Hz: 7.5mm
8.43 Hz
≤
f
≤
200 Hz: 2g
(3M6 acc. to IEC 60721-3-3)
Shock/Bump:
25g/6ms
(3M6 acc. to IEC 60721-3-3)
Directives
EMC
2004/108/EC
Low Voltage
2006/95/EC
RoHS
2002/95/EC
WEEE
2012/19/EC
Standards
Immunity
EN61800-3: 2004 + A1: 2011, 1
st
and 2
nd
envi-
ronment
Emissions
EN61800-3: 2004 + A1: 2011,
3-phase version
Category C2 as standard for
conducted and radiated
emissions
1-phase version
Category C1 as standard for
conducted emissions
Category C2 as standard for
radiated emissions.
The drive can be modified to category C4.
Safety
EN 61800-5-1
Production quality
ISO 9001
Table 32. VACON
®