Safe Torque Off
vacon • 113
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
9
9.8
Maintenance and diagnostics
The STO function or the STO input/output terminals do not need any maintenance.
The following table shows faults that may be generated by the software that monitors the hardware
related to the STO safety function. If you detect any failure in safety functions, including STO, contact
your local VACON
®
supplier.
NOTE!
See Table 36 for detailed fault code descriptions.
If any service or repair has to be conducted on the drive installed, please inspect the
checklist given in Table 49.
During maintenance breaks, or in case of service/repair,
ALWAYS
make sure that the
STO function is available and fully functional by testing it.
Table 50. Fault related to the STO function.
Fault Code
Fault
Cause
Correction
30
Safe Torque
Off
STO inputs in a different
state or both de-ener-
gized
Check cabling