Commissioning
vacon • 63
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6
6.4
Maintenance
In normal conditions, the AC drive is maintenance-free. However, regular maintenance is recom-
mended to ensure trouble-free operation and longevity of the drive. We recommend the table below
is followed for maintenance intervals.
Table 26.
Maintenance interval
Maintenance action
Regularly and according to
general maintenance interval
•
Check tightening torques of termi-
nals.
6...24 months (depending on
environment)
•
Check input and output terminals and
control I/O terminals.
•
Check for corrosion on terminals and
other surfaces.
•
Check the heatsink for dust and clean
if necessary.
6...10 years
•
Change the main fan.
12...24 months
•
Charge capacitors, only after long
storage times or long down times
without supply: contact your nearest
VACON
®
service center.