Solar pump application
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
10.5
Photovoltaic system dimensioning
The photovoltaic system has to be dimensioned in order to not exceed the values specified in the
tables below.
Table 57. Diode specification, Mains voltage 3AC 380-480V, 50/60 Hz, up to 800V in VDC
AC drive
Diode specifications
Enclosure
size
AC drive type
min. IFav [A]
Min. Voltage rating
MU3
0009
20
1200 V
0012
28
0016
36
Table 58. VACON
®
20 X (208…240V 3AC 50/60Hz) DC-link input ratings
Enclosure
size
AC drive type
DC supply [V]
Max. Recommended PV Array Power
[kW]
MU3
0011
234 … 400V
DC
No tolerance permissible,
0%
4.4
0012
6.0
0017
8.0
Table 59. VACON
®
20 X (208…240V 1AC 50/60Hz) DC-link input ratings
Enclosure
size
AC drive type
DC supply [V]
Max. Recommended PV Array Power
[kW]
MU2
0004
234 … 400V
DC
No tolerance permissible,
0%
1.5
0005
2.2
0007
3.0
Table 60. VACON
®
20 X (380…480V 3AC 50/60Hz) DC-link input ratings
Enclosure
size
AC drive type
DC supply [V]
Max. Recommended PV Array Power
[kW]
MU3
0009
436 … 800V
DC
No tolerance permissible,
0%
8.0
0012
11.0
0016
14.0