vacon • 38
Power cabling
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Figure 26. NPT-to-metric threads adapter.
Tightening torque of NPT adapters to metric threads cable entries:
NPT adapter order information:
M20 -> ADEC M20-T12
M25 -> ADEC M25-T34
11
•
Teflon tape has to be used to ensure that you get a water tight seal on pipe
joints.
12
•
Start by cleaning the male threads at the end of the pipe with a clean rag.
•
Place the end of the Teflon tape on the second thread in and hold it in
place with one hand.
•
Wrap the tape in the same direction of the threads.
•
Keep tension on the tape and wrap it several times working away from the
end of the NPT pipe.
•
When you have finished wrapping the Teflon smooth the loose end down
into the threads.
•
Screw the NPT-to-metric adapter on the cable entry using the proper
tightening torque. See Table 17 for more details.
•
Screw the NPT pipes on the adapters.
Table 17. Tightening torque of NPT adapters to metric threads cable entries.
Enclosure
size
Thread male
metric
Thread female
NPT
Tightening torque
[Nm]
lbs-in.
MU2
M20
1/2”
2.0
17.7
M25
3/4”
4.0
35.5
MU3
M25
3/4”
4.0
35.5
The VACON
®
20 X drive is IP66/Type 4X rated. To keep this rating, the use of a sealed
conduit is required: if the approved conduit is not used, all warranty claims against wa-
ter will be void.