Technical data
vacon • 71
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7
Table 34. Technical information on Relays.
Relays
Terminal
Signal
Technical information
22
Relay output 1
*
*
If 230VAC is used as control voltage from the output relays, the control circuitry
must be powered with a separate isolation transformer to limit short circuit current
and overvoltage spikes. This is to prevent welding on the relay contacts. Refer to
standard EN 60204-1, section 7.2.9
Switching capacity
250VAC/3A
(only earthed network allowed)
23
24
Relay output 2*
Switching capacity
NO 250VAC/5A
NC 250VAC/3A
(only earthed network allowed)
25
26