3.1.10 Fire reset event
generated if...
•
a fire reset input is opened
activates...
•
for 1 second the outputs programmed as fire reset that have at least one zone shared with
the input that generated the event
is stored...
•
in the event log
besides...
•
stops the respective fire alarm
•
resets the fire alarm volatile memory
•
turns off the LED on the keypads and readers that signalled the event
Warning:
in case of “fire alarm” signalling and subsequent alarm manual resetting, environmental conditions
have to be restored in premises where the alarm was generated and the detector has to be checked to have been
armed again in order to be able to detect a new alarm situation.
3.1.11 Technological
event
System 1067 provides the capability to
manage some domotics (heating activation, garden irrigation management, etc.)
functions through “technological events”, “door opener event” and “courtesy light event”.
“Technological events” and “courtesy light event” are always active (24H), while “door opener event” is only active when
zones are not active.
generated if...
•
a technological input is opened
activates...
•
the outputs programmed as Technological that have at least one zone shared with the input
that generated the event
•
the communicator for voice, SMS modem or numerical sending of the respective
technological Service message (if programmed)
is stored...
•
in the event log
is held...
•
until is open at least one of the inputs programmed as Technological with at least one zone
shared with the input
3.1.12 Door
Opener
Event
generated if...
•
a Burglar input is opened belonging to one or more zones to which Door Opener additional
function was enabled. All zones associated to the input must be not active.
•
a key programmed as “access control” is inserted associated to one or more zones. All zones
associated to the key must be not active.
activates...
•
Door Opener programmed outputs associated to at least one input zone or key zone.
is stored...
•
into Event Log in case of actuation caused by a key
is held...
•
about 2 seconds
3.1.13 Courtesy Light Event
generated if...
•
a Burglar input is opened belonging to one or more zones to which Courtesy Light additional
function was enabled.
activates...
•
Courtesy Light programmed outputs associated to at least one input zone.
is held...
•
about 3 minutes
3.1.14 Failure alarm from a Failure input
System 1067 can be paired to the control of devices provided with a “failure” output.
generated if...
•
an input programmed as Failure is opened
The alarm is generated regardless of the zones status (24h).
activates...
•
the outputs programmed as Failure that have at least one zone shared with the input that
generated the event
•
the communicator for voice, modem or numerical sending of the respective Failure message
(if programmed)
is stored...
•
in the event log
•
into failure and fault list
is displayed...
•
with the failure yellow LED on the keypads
•
with the yellow LED on the readers
is stopped by...
•
when the input programmed as Failure is closed
after the solution of
the problem the
control panel...
•
it activates the communicator for numerical sending of the respective message of failure
alarm end (if programmed)
•
turns off the failure LED on keypads and readers
•
stores in the event log the failure end
•
deactivates the outputs programmed as failure