For this condition the display is divided
into three text panels, shown on fig.1
•
The first panel displays
information on zones and on the fire
control panels in fire condition. A
flashing heading with the text FIRE and
the total number of zones in fire
condition appear [1].
The panel is subdivided into two text
fields, each providing two lines. The
first line displays information on the first
zone and the fire control panel in fire
condition, the second line provides
information on the last zone and the
fire control panel for the repeater is in
fire condition.
The text fields provide the following information:
-
The sequence number of the indicated fire condition (pos.2, fig.2).
-
The phase of Fire condition detected by the fire control panel in this particular zone (pos.3,
fig.2).
-
The zone number (pos.4, fig.2).
-
The address of the fire control panel in fire condition (pos.5, fig.2).
-
The remaining time in seconds before the fire control panel proceeds to phase Fire
condition stage II (indicated only in Fire condition stage I) (pos.6, fig.2).
-
Text message for the respective zone (pos.7, fig.2).
If the fire control panel has entered Fire condition in more than two zones, the rest of the text
messages for fire condition are suppressed. They can be displayed in the first (upper) field by
pressing the buttons on the right side
and
.
•
The second panel provides information on devices in fire condition.
In the head part is displayed the total number of devices in fire condition (pos.8, fig.2).
The panel itself is subdivided into three text fields, each providing two lines. The upper two-line field
displays information on the first device that has detected fire condition; the middle two-line field
displays information on the second device in fire condition, the bottom two-line field – information on
the last device.
The text fields provide the following information:
-
The sequence number of the device in fire condition (pos.9, fig.2).
-
The fire alarm loop where the device is integrated to (pos.10, fig.2).
-
The zone number (pos.11, fig.2).
-
The device address in the fire alarm loop (pos.12, fig.2).
-
The remote fire control panel address that is in Fire condition (pos.13, fig.2).
- Text message for the respective device (pos.14, fig.2).
The second line of each field displays text messages relevant to this particular device.
If more than three devices are activated due to fire condition, the rest of the messages are
suppressed. However, they can be displayed in the first two upper fields, by pressing the buttons on
the right side.
•
The third panel (the bottom one) displays information on the numbers of faults and disables –
total number and for the outputs (monitored outputs and addressable output devices). (pos.15, fig.1).
Mode: DAY REP ActInp 0000
11:11:08
Thu 25 Aug 2011
FIRE CONDITION
ZONES IN FIRE:
3
>
1 Phase 2 Zone 001 REM #2
Zone 001
3 Phase 1 Zone 002 REM #4
Zone 002
Time Fire Phase2: 120
Devices in Fire
Total number:
4
1 Loop 01 Zone 001 Addr 001 Object: REM #2
Point 1.001
2 Loop 02 Zone 003 Addr 001 Object: REM #2
Point 2.001
4 Loop 01 Zone 002 Addr 002 Object: REM #4
Point 1.002
Faults total: 00000/0000*
Disables total: 000
Failed Outputs:00000
Disabled Outputs:000