UniPOS Repeater IFS7002R
Instruction Manual Page 39
Revision 2/16.11.09 Of 62
successful check of the repeater
connection with the subsequent fire
control panel connected to it:
-
If the value is 0 - no “Beep” is
released
-
If the value is N>0, each N
th
successful check is signaled by
“beep”. For example, if it is
entered N=1, each check-
performed at each “Period of
check, [s]” seconds will be
signaled.
MaxErrRec
1
÷
20
3
Number of CAN-communication errors
when receiving telegrams from fire
control panels. After this number is
reached the respective fire control panel
is regarded as suspended (temporarily)
from CAN network and a signal is
released for a Fault condition of the type
“Connection failure with remote fire
control panel with address…”
MaxErrSend
1
÷
20
3
Number of CAN-communication errors
when sending telegrams to fire control
panels. After this number is reached the
respective fire control panel is regarded
as suspended (temporarily) from CAN
network and a signal is released for a
Fault condition of the type “Connection
failure with remote fire control panel with
address…”
Check period, [s]
1
÷
250s
5s
A time period is entered. After it elapses
the repeater scans the status of the
CAN-communication with the connected
fire control panels – including the
suspended ones form the network at the
moment.
Rate, [KBits/s]
640, 320, 213,
160, 128, 106,
91, 80, 71, 64,
58, 53, 49, 45,
42, 40, 35, 32,
29, 26, 24, 22,
21,20, 17, 16,
14, 13, 11, 10
[KBits/s]
80
The communication rate in the network;
Priority communic.level
“Main”
“Subordinate”
subordinate
The location of the repeater that is being
set up is specified within the structure of
the local CAN network that is being
established. One of the repeaters or the
fire control panels IFS 7002 within the
network should be specified to be
Master, and all remaining repeaters and
fire control panels – “Subordinate”
(Slave). The master repeater or fire