UniPOS Repeater IFS7002R
Instruction Manual Page 4
Revision 2/16.11.09 Of 62
1.
Repeater IFS7002R is a device supplementing the range of IFS7000 series devices as it expands the
potentials of systems established based on Fire Control Panel IFS7002.
Introduction
The device is suitable in premises where:
-
The person, that are expected to find and initially respond to the fire condition and/or fault
condition alarm are situated on different place from the location of the fire control panel/s.
-
Fire control panels, located in different buildings have to be monitored and controlled from
one location.
-
The fire control panel or panels are monitored from several locations simultaneously.
2. Function
The repeater IFS7002R is designed to optimize the performance of users. The repeater is a network
made up of connected remote fire control panels IFS7002 and other repeaters IFS7002R.
Repeater IFS7002R:
-
Receives and displays information about the status of remote fire control panel/panels.
-
Formed a control action to remote areas of fire stations for their forced exit from the state
"Fire".
3. Technical data
3.1 Performance
•
Number of the control panels or/and repeaters connected to IFS7002R – up to 31.
•
Indicating fire condition and/or fault condition from each zone or fire detector from the
connected to it remote panels.
•
Full range of commands available for sending to the remote fire control panels.
•
Remote panels’ parameters review and full access to the setup of these parameters.
•
User-friendly menu dialogue for easy and convenient operation.
•
Graphic LCD display for visualizing the remote fire control panels status.
•
Dynamic keypad based on a Touch-screen panel.
•
LEDs and sound indication for faults, fire and other operation modes.
•
Built-in real time clock.
•
Interfaces for communication with the fire control panels IFS7002 – CAN 2.0B connected to it.
•
Interfaces for communication with PC – RS-232 directly or LAN via a converter RS232 – LAN
Ethernet.
•
Possibility for connection of PC keyboard for setting up and programming.
3.2. Indications of registered events
3.2.1. Light indication
- LED
3.2.2. Text message
- LCD display, 320
х 2
40 points,
backlit
3.2.3. Sound signaling
- built-in sounder
3.3. Power supply
3.3.1. From the fire control panel connected with the repeater IFS7002R
Voltage
- (23±7)V DC
Maximum current value
- 180 m
А
3.3.2. From external power supply (in compliance with EN54-4)
Voltage
- (12 - 30)V DC
Maximum current value
- 310 m
А
3.4. Dimensions
- 290x219x46mm
3.5. Weight
- 1 kg
4. Contents of delivery
•
Repeater IFS7002R
- 1 pc
•
CD with Instruction manual and Instruction for staff - 1 pc
•
Packing
- 1 pc