UniPOS
Fire Control Panel FS5200
Instruction manual
Page 41
Revision 8/07.17
of 69
04 Current threshold above which Fire condition stage I is
detected in a line:
“CCC” contains the current in mA - 1 to 80mA.
05 Current threshold above which Fire condition stage II is
detected in a line:
“CCC” contains the current in mA - 1 to 80mA.
06 Current threshold above which Short circuit is detected in a
line:
“CCC” contains the current in mA - 1 to 80mA.
07 Current threshold below which a break in a line is detected:
“CCC” contains the current in mA - 1 to 80mA.
08 Logical AND in a line
The field
“ХХ” may contain 00 (the current line is not in
Logical AND dependency by another line) or a digit from 01
to 32 (number of the line in Logical AND dependency by the
current line)
– see 6.3.
The modification of parameter Logical AND has the following special features:
A line can not be set to Logical AND dependency by itself
– button
is not active in
this case;
A line can not be set to Logical AND dependency by a line that has already been set to
such dependency by a third line
– button
is not active in this case either;
A line can not be set to Logical AND dependency by a line that does not exist in the current
configuration (for example dependency on Line 31 and the configuration has 24 lines)
–
button
is not active in this case either;
A line can not be set to Logical AND dependency by a line connected to another Module
(lines 1-16 are connected to the Basic module, Lines 17-32 are connected to the Additional
module)
– button
is not active in this case;
Where a line is set to Logical AND dependency by another line, the second line is
automatically set to the same dependency by the first line
– in the parameter Logical AND
of the second line is saved the number of the first line;
Where a line exits the Logical AND dependency, the second line exits the dependency by
the first line too
– in the parameter Logical AND of the line is saved “0”;
The Logical AND dependency can cover only two fire alarm lines
– if, before the
modification of the parameter Logical AND, it contained a number of a third line, the third
line automatically
exits the dependency (in the third line’s parameter Logical AND is saved
“0”).
> Set Parameters <
> Line NN <
Logical AND ХХ
> Set Parameters <
> Line NN <
Current Interr CCmA
> Set Parameters <
> Line NN <
Current Short CCmA
> Set Parameters <
> Line NN <
Current Fire2 CCmA
> Set Parameters<
> Line NN <
Current Fire1 CCmA