Instruction manual
Page 34
Revision 8/07.17
of 69
03 Period for transition from Fire condition stage I to Fire
condition stage II:
The field
“NN” contains the number of the line;
“SSS” contains the period in seconds - 0 to 255s.
04 Current threshold above which Fire condition stage I is
detected in a line:
The field
“NN” contains the number of the line;
“CCC” contains the current in mA - 1 to 80mA.
05 Current threshold above which Fire condition stage II is
detected in a line:
The field “NN” contains the number of the line;
“CCC” contains the current in mA - 1 to 80mA.
06 Current threshold above which Short circuit is detected in a
line:
The field “NN” contains the number of the line;
“CCC” contains the current in mA - 1 to 80mA.
07 Current threshold below which Interruption in a line is
detected:
The field “NN” contains the number of the line;
“CCC” contains the current in mA - 1 to 80mA.
08 Logical AND dependency of a line:
The field
“NN” contains the number of the line;
“ХХ” may adopt value 00 (the line is not in Logical AND
dependency by another line) or values from 01 to 32
(number of the line with Logical AND dependency by the
current line).
09 Menu Controllable outputs in Fire condition stage II in the
line:
The field
“NN” contains the number of the line.
The menu contains 1 or 2 information screens depending on
the available controllable outputs:
The field
“KK” contains the number of the controllable
output;
“ХХ” can contain “No” (the controllable output will not be
activated in Fire condition stage II) or “Yes” (the controllable
output will be activated).
10 Menu Relay outputs in Fire condition stage I in the line
The field “NN” contains the number of the line.
Line NN N10
Relays F1
Line NN N09
F2 Ctrl Out KK ХХ
Line NN N09
Ctrl Outs F2
Line NN N08
Logic & ХХ
Line NN N07
Current Interr CCmA
Line NN N06
Current Short CCmA
Line NN N05
Current Fire2 CCmA
Line NN N04
Current Fire1 CCmA
Line NN N03
Time F1-F2 SSSs