UniPOS
Fire Control Panel FS5200
Instruction manual
Page 14
Revision 8/07.17
of 69
Table 2
Means of control
Condition of the fire
control panel
Access
level
Operation
Key for access to
Level 2
Level 1
Position
Level 2
Position
Button
Reset of
line
Fire condition
Level 2
To exit Fire condition in a line, indicated on
the LDC display
Button
Outputs
Fire condition, phase
Fire condition stage I
Level 1
To force proceeding to phase Fire condition
stage II
Fire condition, phase
Fire condition stage I
Level 2
- if activated outputs for fire condition are
available
– to suppress the outputs;
- if no activated outputs for fire condition
are available
– to force proceeding to
phase Fire condition stage II
Fire condition, phase
Fire condition stage II
Level 2
- if activated outputs for fire condition are
available
– to suppress the outputs;
- if activated outputs for fire condition are
not available
– to activate any suppressed
outputs
Button
Inspection
Fire condition, phase
Fire condition stage I
Levels 1
and 2
To add inspection time
Button
Alarm
Fire condition and
Fault condition*
Level 1
To suppress /activate the local sounder
Button
Menu
Duty Mode, Fire
condition, Pre-fire
condition, Fault
condition*, Test mode
and Disabled
component
Levels 1
and 2
To enter Information and Control mode
Information and
Control
Levels 1
and 2
- To enter the selected menu
- To execute the selected command
- To save a modified parameter
SetUp
Level
3А
Button
Down
Fire condition
Levels 1
and 2
To display the next message for fire
condition
Information and
Control
Levels 1
and 2
- To display the next element of the menu
- To move the cursor
- To modify the selected parameter
SetUp
Level 3А
Button
Up
Fire condition
Levels 1
and 2
To display the previous message for fire
condition
Information and
Control
Levels 1
and 2
- To display the previous element of the
menu;
- To modify the selected parameter
SetUp
Level 3А
Button
Cancel
Information and
Control
Levels 1
and 2
- To exit a function without saving changes
in the parameter; the command will not be
executed
- To exit the current menu and to move to
an upper hierarchy menu
SetUp
Level 3А
* Not effective in Fault condition (fatal fault condition except for New configuration).