UniPOS
Fire Control Panel FS5200
Instruction manual
Page 18
Revision 8/07.17
of 69
8.3.5. Buttons
(Down) and
(Up)
If there are suppressed messages for fire condition they can be displayed in the first field of the
LCD display using buttons
and
situated on the front panel.
Press button
to display the next text message for fire condition. When the last text
message is reached, press button
to display the first message.
Press button
to display the previous text message for fire condition. When the first
message is reached press button
to display the last message.
If a suppressed message is displayed, 20s after the button is pressed for the last time the first
message for fire condition will restore automatically.
8.3.6. Button
(Menu)
Press the button to enter Information and Control Mode.
8.3.7. Button
(Cancel)
When Fire condition is combined with Information and Control Mode, press the button
continuously to cancel the Information and Control Mode; the first field will then display information on
the first fire alarm line in Fire condition.
9. Pre-Fire condition
9.1. Description
Pre-Fire condition ensures the correct operat
ion of the Function “Logical AND” for two lines (see
section 6.3).
9.2. Indication
9.2.1. LED and sound indication
The common indicator
(Fire condition stage I) illuminates in continuous red light to indicate
the condition.
The local sounder emits discontinuous asymmetrical signal - 4 sound impulses for 1 s, then
pause for 1s. If the sound indication has been suppressed by button
(Alarm), the LED indicator
on the button illuminates in steady red light.
9.2.2. Text message
The message DUTY and the real time are displayed on the
LCD display.
This message can be suppressed from the screen for Fire Condition. To display the suppressed
messages enter Information and Control Mode (see section 13.6).
9.3. Using the keypad
9.3.1. Button
(Alarm)
Press the button to:
Switch off the local sounder if it responded to Fire condition/Pre-fire condition or Fault
condition;
To activate the local sounder of the fire control panel is in Fire condition/Pre-fire condition or
Fault condition and the local sounder is suppressed by a previous push on the same button;
The LED indicator on the button illuminates if the local sounder is suppressed after response
to Fire condition/Pre-fire condition or Fault condition;
Duty 17:05:34
Thursday 16-10-2003