UniPOS
Fire Control Panel FS5200
Instruction manual
Page 27
Revision 8/07.17
of 69
13.4. Menu
Lines in test
Select the menu from the screen:
The menu contains information screens with suppressed messages for lines in test.
Where no lines in test are available appears the following
information screen:
Where some lines in test are available the following information
screen appears:
(The field
“NN” contains the consecutive number of the
message for a line in test;
“EE” contains the total number of lines in test;
“ХХ” contains the number of a specific line in test )
13.5. Menu
Status
Select the menu from the screen:
The menu contains information screens with the status of lines and controllable outputs.
Information screen for the status of the line appears:
(The field
“NN” contains the number of the selected line
“Status” contains information on its status)
Information screen for the status of the controllable output
appears:
(The field
“NN” contains the number of the selected controllable
output;
“Status” contains information on its status)
The following statuses are possible:
Normal
– for a line/controllable output in normal state;
Fire1
– for a line in phase Fire condition stage I (only when no fault condition is registered);
Fire2 - for a line in phase Fire condition stage II (only when no fault condition is registered);
PreFire - for a line set in LOGICAL AND dependency, an automatic fire detector is activated
in this line and a second fire alarm line is expected to enter Fire condition (only when no fault
condition is registered);
Removed FD
– for a line with removed fire detector;
Break
– for a break in a line/ controllable output;
Short circuit
– for short circuited line/controllable output ;
None
– for a line/controllable output not present in the configuration (the status appears also if
the control microprocessor for a line/controllable output fails).
Status
cONN Status
Status
LnNN Status
04 Status
05 Pre-fire
Test NN of EE
Line XX
Lines in Test
No Lines in Test
03 Lines in Test
04 Status