UniPOS
Fire Control Panel FS5200
Instruction manual
Page 13
Revision 8/07.17
of 69
Fire condition stage I in both lines
– if there is an activated automatic fire detector in the other
line, i.e. the fire control panel has already entered Pre-Fire condition in the other line.
Exit from Pre-Fire condition in a line is done automatically only:
Upon activation of automatic fire detector in a line that has settled “Logical AND” dependence
to a particular line, within 60 s after entering Pre-Fire condition, the fire control panel enters
Fire condition stage I in both lines;
Upon activation of manual call point in the line that has settled dependence to a particular line
according the function “Logical AND”, within 60 s after entering Pre-Fire condition, the fire
control panel enters Fire condition stage I in this particular line, and Fire condition stage II in
the first line;
Table 1
Conditions of the fire control panel
Indication
All conditions -
The fire control panel is power supplied
Indicator
Power supply
–
continuous green light
All conditions
Indicator
Day Mode
–
continuous yellow light
Fire condition, phase Fire condition stage I
Common indicator
Fire condition
stage I
– flashing red light
Fire condition, phase Fire condition stage II
Common indicator
Fire condition
stage II
– flashing red light
Fire condition, phase Fire condition stage I
–
inspection time has been entered
Indicator
Inspection
–
continuous green light
Fire condition and Fault condition -
sounders have been suppressed
Indicator
Stop Alarm
–
continuous red light
Fire condition -
outputs for fire condition have been suppressed
Indicator
Suppressed outputs-
continuous red light
Fault condition -
All faults except for Low battery
Common indicator
Fault condition
– flashing yellow light
Fault condition
–
System fault and New configuration
Indicator
System fault
–
continuous yellow light
Fault condition -
Fault in mains supply
Indicator
Fault in mains supply -
flashing yellow light
Fault condition -
Fault in the backup batteries or in the charger
Indicator
Backup battery fault
-
flashing yellow light
Fault condition -
Fault in a controllable output
Indicator
Out of order/Disabled
controllable output
–
flashing yellow light
Disabled component -
Disabled controllable output
Indicator
Out of order/Disabled
controllable output
–
continuous yellow light
Disabled component -
Disabled line or controllable output
Indicator
Disabled component
-
continuous yellow light
Test condition
Indicator
Test
–
continuous yellow light
Fire condition
Local sounder
– continuous signal
Pre-Fire condition
Local sounder
– discontinuous signal:
4 sound impulses for 1s, followed by
1s break
Fault condition - All faults except for Low battery
Local sounder
– discontinuous signal:
1s sound 1s break
Fault condition -
Low battery
Local sounder
– discontinuous signal:
1s sound 3s break