35
Instructions for the installer
3.17 -
DESCRIPTION OF THE E8 HEATING CONTROLLER’S MENUS
AND OPERATING LEVELS
For further information please refer to the “USERS INSTRUCTIONS” supplied with the E8.5064 heating controller.
MAIN AREAS MENU
General
Value selection summary
Service = for service engineers
Date/Time/Holiday = for users
Display
System value display (e.g. sensor values and setpoints). No
adjustments can be made. Operating errors are therefore
excluded in this area.
User
Summary of the settings which can be made by the user.
Time programs
Summary of the time programs for heating circuits, the hot water
circuit and the supplemental functions.
Expert
Summary of values for which expert knowledge is required to
make settings (installer).
The values in the expert level are protected by a code number
(incorrect settings can cause serious malfunctions or system
damage).
Expert FA (only for FA via BUS)
Summary of the values transmitted by the automatic firing
device (BMM).
LEVELS
The settings in the different areas are divided into operating
levels:
- INSTALLATION
- HOT WATER
- HEAT CIRCUIT I
- HEAT CIRCUIT II
- SOLAR/MF
Installation
All display values and settings that relate to the heat generator
or the entire system and cannot be assigned to a consumer
circuit.
Hot water
NOTE: The domestic hot water adjustment is
controlled by the electronic board fitted on the boiler.
Heat circuit I/II
All display values and settings that relate to the associated
consumer circuit (also for example, as decentral hot water).
Solar/MF
All indicator and set values that relate to solar energy recovery
and settings for the multifunction relay.
Operation is divided into different main menu areas:
- General
- Display
- User
- Time programs
- Expert
Opening the hinged control panel cover automatically
takes you to the display and indicator area.
• The current area “DISPLAY” appears in the display for a
short time.
• After the set time has elapsed the display switches to the
current operating level “INSTALLATION”.
• This is displayed for a short time when you switch to a new
area.
Use the rotary knob to select or adjust the desired le-
vel.
Press Prog key! => Open/select level
Use the rotary knob to select the desired level
Press Prog button! => Select value
LED lights up => adjustment can now be made
Change value using rotary knob
Press Prog key! => Store value - LED goes off
General
SERVICE
DATE/TIME/HOLIDAY
Turn in an anticlockwise direction
Turn in an clockwise direction
1
Open the
hinged
control
panel cover
Display
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
User
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
Time progr
CIRCL TIME
HOTW-PROG
HTG-PROG I
etc
Expert
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
Expert FA
INSTALLATION
Summary of Contents for Alkon Cargo 35