Instructions for the installer
3.13 - INITIAL LIGHTING
Preliminary checks
The first ignition must be carried out by a
qualified technician.
Failure to do so could
cause injury to persons, animals or damage
to property. UNICAL shall not be held liable
for any injury and/or damage.
Before lighting the boiler check that:
-
the boiler installation has been carried out in accordance
with the specific Standards UNI 7129 and 7131 for the gas
part and to the Standards CEI 64-8 and 64-9 for the electri-
cal part;
-
the combustion air inlet and the discharge of the products
of combustion occur in the correct way in accordance to
the specific Standards in force (UNI 7129/7131);
-
the gas supply system is correctly dimensioned for the
boiler’s output;
-
the boiler’s electrical supply is 230 V - 50 Hz;
-
the system has been filled with water (pressure registered
on the gauge 0,8/1 bar with pump not running);
-
any of the system’s on-off valves are open;
-
the mains supply gas corresponds to the one which the
boiler has been calibrated for: otherwise convert the boiler
to use the available gas (refer to section: “GAS CONVER-
SION”); this operation must be carried out by a qualified
technician in compliance to the regulations in force;
-
the gas supply cock is open;
-
there are no gas leaks;
-
the external mains supply switch is on;
-
the boiler system’s safety valve is not blocked and that it is
connected to the sewage system;
-
the condensate drain siphon has been filled with water;
-
there are no water leaks;
-
all the necessary ventilation conditions and minimum clea-
rance distances are guaranteed for subsequent servicing
in case the boiler is sited in a cupboard compartment or in
a narrow space.
Lighting and shutting down procedures
For lighting and shutting down the boiler refer to the “USER’S
INSTRUCTIONS GUIDE”
Information to be passed on to the user
The user must be instructed on the use and operation of his
boiler and in particular detail:
•
Hand over to the end user the booklet: “USER’S INSTRUC-
TIONS GUIDE”, as well as all the other literature relative to
the appliance and placed in the envelope contained in the
packaging.
The user must retain this literature for any
future reference.
•
Inform the user of the importance of the air vents and of
the flue outlet system, stressing the fact that absolutely no
alterations can be made.
•
Inform the user regarding the control of the system’s water
pressure and how to restore it to the correct value.
•
Explain and demonstrate to the user the correct function
and adjustment of the temperature, thermostats and radia-
tors for the economic use of the system.
•
Remind the user that in order to comply to the regulations
in force the boiler has to be inspected and serviced an-
nually and that it must undergoe a combustion analysis
every two years (as indicated by the national legislation).
•
If the appliance is sold or transferred to another owner or if
the present user moves home and leaves the appliance
installed, ensure yourself that the manual always follows
the appliance so that it can be consulted by the new owner
and/or installer.
DANGER!
Before commissioning the appliance fill
up the siphon through the appropriate fil-
ling hole and check the correct drainage
of the condensate.
If the appliance is used with the conden-
sate drain siphon empty this could cause
intoxication caused by the leakage of the
flue gasses.