4
TRI93.134.5
www.tritium.com.au
Veefil®isaregisteredtrademarkofTritiumPtyLtd.©2015TritiumPtyLtd
USA only:
3ø: 4AWG
Use 90°C Copper Wire
Use 4 AWG insulated
grounding conductor
1ø: 18AWG
Use 90°C Copper Wire
An insulated grounding conductor that is
identical in size, insulation material and
thickness to the grounded and unground
-
ed branch-circuit supply conductors ex-
cept that it is green with or without one
or more yellow stripes is to be installed
as part of the branch circuit that supplies
the unit or system. This grounding con-
ductor is to be grounded to earth at the
service equipment or, when supplied by a
separately derived system, at the supply
transformer.
Input:
Worldwide (excluding USA):
3ø WYE CONNECTED
230/400V, 240/415V ±10%
50Hz
55kW
USA Only:
3ø WYE CONNECTED
277/480V ±10%
60Hz
52kW
1ø, 120V
60Hz
250W
The Veefil must be connected to a
circuit provided with appropriate
branch circuit over-current protection
in accordance with the National Elec-
trical Code, ANSI/NFPA 70.
Tightening Torque:
Wiring terminals:
4.0 Nm/35 lb-in
Service Hatch:
1.0 Nm/8.75 lb-in
Operating Temperature:
-20° to 50°C / -4° to 131°F
(-35°/-31°F optional)
Maximum Ambient
Temperature:
55°C /131°F
Weather Rating:
IP65 Electronics Enclosure
NEMA Type 3R
Important Safety Instructions and
Specifications. Save these instructions