3
TRI93.134.5
www.tritium.com.au
Veefil®isaregisteredtrademarkofTritiumPtyLtd.©2015TritiumPtyLtd
Important Safety Instructions and
Specifications. Save these instructions
This manual contains important instruc
-
tions for the Veefil® electric vehicle fast
charger models;
TRI93-50-01, 50kW dual DC (worldwide
excluding USA).
TRI93-50-01-US, 50kW dual DC (USA
market only).
TRI93-50-02, 50kW DC+AC (worldwide
excluding USA).
Model TRI93-50-02 specifications, site
configuration and installation procedures
are described in pages 30 to 38.
These instructions must be followed
during installation, operation and mainte
-
nance of the unit.
CAUTION
The Veefil fast charger must be installed
and serviced only by qualified electrical
personnel.
To achieve EMC compliance, the chassis
of the Veefil must be bonded to Earth
locally at the charger.
Grounding Instructions
This unit is to be connected to a ground
-
ed, metal, permanent wiring system; and
an equipment-grounding conductor is to
be run with circuit conductors and
connected to equipment-grounding
terminal or lead on battery charger.
Connections to the battery charger shall
comply with all local codes and
ordinances.
All pertinent national, regional and local
safety laws and regulations must be
observed when installing and commis-
sioning the Veefil fast charger.
Identifying Symbols
CAUTION
RISK OF ELECTRIC SHOCK
Equipment Grounding
Conductor Symbol
ø
Phase Symbol
Alternating Current Supply
Symbol
Wiring Size
Worldwide (excluding USA)
3ø: 25mm
2
Use 90°C Copper Wire
Take care to observe local regulations
regarding wiring different circuits in the
same conduit, including the ethernet
link if used. In general all conductors
occupying the same conduit shall have
an insulation rating equal to at least the
maximum circuit voltage applied to any
conductor within the conduit.