65
CHAPTER
1
3
CHAPTER 13 - EXTERNAL MODULATING CONTROL
The PRESTIGE Solo can directly accept an analog
0-10 VDC signal from an external modulating boiler
controller to control the firing rate.
13.1. Wiring the Modulating Controller
Run two 18 gauge wires from the external modulating
boiler controller’s 0-10 VDC boiler output to low voltage
terminals X5-1&2 located at the bottom of the ACVMax
control module, as shown in
Fig. 23 on page 36.
. This
signal will both enable and modulate the boiler. No wir-
ing is required at the thermostat terminals.
External modulating control will only function if the
external modulating controller is properly wired to the
PRESTIGE Solo as follows:
• X5-1 = +
• X5-2 = -
Ensure that the polarity of the connections
from the external modulating boiler controller
to the boiler are correct. Reversed polarity will
lead to no response from the boiler.
NOTICE
13.2. ACVMax Programming
The ACVMax control module must be programmed to
accept the 0-10 VDC signal from the external modulat-
ing boiler control.
1. Use the Heating EZ Setup function to set CH De-
mand to 0-10V Modulation Signal. Reference
Sec-
tion 9.7 on page 46.
13.3. Programming of External Modulating
Control
The external modulating control must be programmed
to send 2 VDC to enable the boiler and run it at low fire,
and 10 VDC to run the boiler at high fire. Once the con-
trol enables the boiler, it must wait 30 seconds to allow
the burner to stabilize before modulating the boiler.
Factory ACVMax Settings
HEATING SETTING
FACTORY
DEFAULT
MINIMUM
SETTING
MAXIMUM
SETTING
EZ SETUP RESET
INSTALLER RESET
Heating Operation
Enabled
3
Demand Type
Thermostat &
Outd. Curve
3
3
Absolute Max CH Setpoint
188°F [87°C]
68°F [20°C]
188°F [87°C]
CH1 Maximum Setpoint
140°F [60°C]
68°F [20°C]
188°F [87°C]
180°F [82°C]
3
CH1 Minimum Setpoint
80°F [27°C]
60°F [15°C]
188°F [87°C]
3
3
Outdoor Curve Coldest Day
10°F [-12°C]
-30°F [-34°C]
50°F [10°C]
3
Outdoor Curve Warmest Day
64°F [18°C]
60°F [15°C]
78°F [25°C]
3
CH2 Circuit
Enabled
3
CH2 Maximum Setpoint
140°F [60°C]
68°F [20°C]
194°F [90°C]
3
3
CH2 Minimum Setpoint
80°F [27°C]
60°F [15°C]
190°F [88°C]
3
3
Warm Weather Shutdown
Off
Off
78°F [25°C]
3
3
Circulation Pump Permanent
Disabled
3
CH Post Pump Time
5 Minutes
Off
20 Minutes
3
Freeze Protection
Enabled
3
Frost Protection Setpoint
-22°F [-30°C]
-22°F [-30°C]
50°F [10°C]
3
Parallel Shift Value
0°F [0°C]
0°F [0°C]
144°F [80°C]
3
CH Call Blocking
2 Minutes
0 Minutes
30 Minutes
3
Summary of Contents for PRESTIGE Solo PA 110
Page 2: ...INTENTIONALLY LEFT BLANK...
Page 10: ...INTENTIONALLY LEFT BLANK...
Page 22: ...INTENTIONALLY LEFT BLANK...
Page 36: ...INTENTIONALLY LEFT BLANK...
Page 44: ...INTENTIONALLY LEFT BLANK...
Page 52: ...INTENTIONALLY LEFT BLANK...
Page 74: ...INTENTIONALLY LEFT BLANK...
Page 76: ...INTENTIONALLY LEFT BLANK...
Page 80: ...INTENTIONALLY LEFT BLANK...
Page 82: ...INTENTIONALLY LEFT BLANK...
Page 84: ...INTENTIONALLY LEFT BLANK...
Page 111: ......