CHAPTER 11 - START-UP PROCEDURES
11.1. Final Checks Before Start-Up
Ø
Read
Chapter 9 on page 41
regarding the oper-
ation of the ACVMax Boiler Management System.
Ø
Verify the PRESTIGE Solo and the boiler system are
full of water and all system components are cor-
rectly set for operation, including the minimum
flow rate through the boiler, see specifications in
Chapter 19 on page 89.
.
Ø
Verify Start-up Preparation items outlined in
Chap-
ter 10 on page 55
have been completed.
Ø
Verify all electrical connections are correct and se-
curely fastened.
Ø
Inspect vent and combustion air piping for signs
of deterioration from corrosion, physical damage or
sagging. Verify combustion air and vent piping are
intact and correctly installed and supported. Refer-
ence the PRESTIGE Vent Supplement.
Ø
Verify burner configuration - Propane only.
• Check for proper labeling on the gas valve and
the rating label for propane configuration.
• If there is doubt on the burner configuration,
remove the gas valve and check for proper pro-
pane gas orifice size. Refer to
Section 6.3.2 on
page 29
for orifice sizes. Refer to
Fig 16, Fig
17 or Fig. 18 on page 31
for location of the
propane gas orifice.
Ø
Ensure the Condensate Drain Assembly is filled
with water.
11.2. PRESTIGE Solo Start-Up
1. Press the ON-OFF button located on the front con-
trol panel to the OFF position. Turn ON the electri-
cal supply/service to the unit.
2. Read and follow the Operating Instructions out-
lined on previous page.
If PRESTIGE Solo Does Not Start Correctly
1. Check for loose electrical connections, blown fuses
on control module, or an open service switch.
2. Verify CH and DHW operation is enabled. A radiator
or faucet icon with an X through it indicates that
function is disabled.
3. Check the system pressure in the Boiler Information
Menu by following the instructions in
Section 9.12
on page 50.
.
4. Is an external limit (if applicable) open? Ensure the
external limit is reset to the closed position.
5. Are the gas supply valves open at the unit and me-
ter?
6. Is incoming gas supply pressure at the unit more
than 5”w.c. and less than 13” w.c. with all gas appli-
ances ON or OFF.
7. Are the heating thermostats set above room tem-
perature?
8. Remove the blower assembly and verify the blower
check valve is moving freely.
If none of these conditions correct the problem, con-
tact Triangle Tube Technical Support.
11.3. Check the PRESTIGE Solo and System
11.3.1 Check Boiler Piping.
• Check Boiler system piping and components for
leaks. If found, shut down the unit and repair im-
mediately.
• Purge any remaining air from the system. Air in the
system will interfere with circulation, creating heat
distribution problems and noise.
11.3.2 Check Vent and Combustion Air Piping.
• Check for a gas-tight seal at every connection and
seam of the vent and combustion air piping.
Venting system must be sealed gas-tight to
prevent flue gas spillage and carbon mon-
oxide emissions, which will result in serious
injury, or death.
11.3.3 Verify Carbon Monoxide Detector
Verify that at least two (2) carbon monoxide detectors
are installed and operating properly. One must be in-
stalled in the mechanical room where the PRESTIGE
Solo is located and another installed in the living area
outside the bedroom(s).
DANGER
Summary of Contents for PRESTIGE Solo PA 110
Page 2: ...INTENTIONALLY LEFT BLANK...
Page 10: ...INTENTIONALLY LEFT BLANK...
Page 22: ...INTENTIONALLY LEFT BLANK...
Page 36: ...INTENTIONALLY LEFT BLANK...
Page 44: ...INTENTIONALLY LEFT BLANK...
Page 52: ...INTENTIONALLY LEFT BLANK...
Page 74: ...INTENTIONALLY LEFT BLANK...
Page 76: ...INTENTIONALLY LEFT BLANK...
Page 80: ...INTENTIONALLY LEFT BLANK...
Page 82: ...INTENTIONALLY LEFT BLANK...
Page 84: ...INTENTIONALLY LEFT BLANK...
Page 111: ......