CHAPTER 14 - CHECK-OUT PROCEDURES
Perform the following check-out procedures
as outlined and check off items as complet-
ed. When procedures are completed, the in-
staller should complete the installation record
in
Chapter 15 on page 69.
q
Boiler system fluid chemistry checked and verified
as outlined in
Section 10.1 on page 55.
.
q
Boiler system was completely flushed to remove
any debris/sediment.
q
Any automatic air vents placed within the system
are open one full turn.
q
Air is purged from the heating zones and boiler sys-
tem piping.
q
If applicable, confirm that the burner has been
properly configured for Propane as outlined in
Sec-
tion
6.3 on page 29
.
q
Thermostat circuit wiring checked and verified that
no voltage is present as outlined in
Section 10.5 on
page 57
.
q
Operating Instructions
on page 58
were followed
during start-up.
q
Combustion levels and flame pattern verified as
outlined in
Section
11.3.5 on page 60
.
NOTICE
q
Measured the rate of input on Natural Gas as out-
lined in
Section 11.3.6 on page 61.
q
Test high temperature limit as outlined in
Section
11.3.7 on page 61.
q
Checked the incoming gas pressure to the PRES-
TIGE Solo to ensure a minimum pressure of 5”w.c
during flow conditions to all gas appliances and a
maximum pressure of 13”w.c during non-flow con-
ditions for Natural and Propane.
q
Adjusted balancing valves and system limit con-
trols to provide design temperatures to the primary
space heating system.
q
In multiple zone applications, adjusted for correct
flow of boiler water to each zone.
q
Checked and verified room thermostat(s) function
properly and the thermostat(s) heat anticipator (if
used) was properly set.
q
Observed several operating cycles for proper oper-
ation of the PRESTIGE Solo and the system.
q
Set the room thermostat(s) to the desired room
temperature.
q
Reviewed all instructions shipped with the PRES-
TIGE Solo with the homeowner or maintenance
personnel.
q
Completed the Installation Record of
Chapter 15
on page 69.
q
Ensure all manuals and other documents are re-
turned to the Installation envelope and given to
the owner for safekeeping.
Summary of Contents for PRESTIGE Solo PA 110
Page 2: ...INTENTIONALLY LEFT BLANK...
Page 10: ...INTENTIONALLY LEFT BLANK...
Page 22: ...INTENTIONALLY LEFT BLANK...
Page 36: ...INTENTIONALLY LEFT BLANK...
Page 44: ...INTENTIONALLY LEFT BLANK...
Page 52: ...INTENTIONALLY LEFT BLANK...
Page 74: ...INTENTIONALLY LEFT BLANK...
Page 76: ...INTENTIONALLY LEFT BLANK...
Page 80: ...INTENTIONALLY LEFT BLANK...
Page 82: ...INTENTIONALLY LEFT BLANK...
Page 84: ...INTENTIONALLY LEFT BLANK...
Page 111: ......