5
CHAPTER
2
CHAPTER 2 - COMBUSTION AIR & VENTING
2.4. Methods of Accessing Combustion Air
Into A Space - Category IV
2.4.1. Indoor Combustion Air
• The methods listed in this chapter for access-
ing Indoor Combustion Air assume that the
infiltration rate is adequate and not less than
.40 ACH.
• For infiltration rates less than .40 ACH, refer-
ence the National Fuel Gas Code (NFPA 54 /
ANSI Z223.1) for additional guidance.
Opening Size and Location
Openings used to connect indoor spaces shall be sized and
located in accordance with the following, see
Fig. 1 below
:
• Combining spaces on the same story.
Each opening
shall have a minimum free area of 1 sq. in./1000 Btu/hr
of the total input rating of all gas utilization equipment
in the space, but not less than 100 sq. inches. One
opening shall commence within 12 inches of the top,
and one opening shall commence within 12 inches
of the bottom of the enclosure. The minimum dimen-
sion of air openings shall be not less than 3 inches.
• Combining spaces in different stories
. The volumes of
spaces in different stories shall be considered as com-
municating spaces where such spaces are connected
by one or more openings in doors or floors having a
total minimum free area of 2 sq. in./1000 Btu/hr of to-
tal input rating of all gas utilization equipment.
NOTICE
2.4.2. Outdoor Combustion Air
Isolating the combustion appliance room from
the rest of the building and bringing in uncon-
taminated outside air for combustion and ven-
tilation is always preferred.
Opening Size and Location
The minimum dimension of air openings shall be not
less than 3 inches
Openings used to supply combustion and ventilation
air shall be sized and located in accordance with the
following:
• One Permanent Opening Method
. One permanent
opening, commencing within 12 in. of the top of
the enclosure, shall be provided as shown in
Fig.
2 below.
The equipment shall have clearances of
at least 1 inch from the sides and 6 in. from the
front of the appliance. The opening shall directly
communicate with the outdoors or shall commu-
nicate through a vertical or horizontal duct to the
outdoors or spaces that freely communicate with
the outdoors and shall have a minimum free area
of the following:
• 1sq. in./3000 Btu/hr of the total input rating of
all equipment located in the enclosures, and
• Not less than the sum of the areas of all vent
connectors in the space.
BEST PRACTICE
Fig. 1 - All Combustion Air from adjacent Indoor Spaces
through Indoor Combustion Openings
Fig. 2 - All Combustion Air from Outdoors Through One
Permanent Air Opening
Summary of Contents for PRESTIGE Solo PA 110
Page 2: ...INTENTIONALLY LEFT BLANK...
Page 10: ...INTENTIONALLY LEFT BLANK...
Page 22: ...INTENTIONALLY LEFT BLANK...
Page 36: ...INTENTIONALLY LEFT BLANK...
Page 44: ...INTENTIONALLY LEFT BLANK...
Page 52: ...INTENTIONALLY LEFT BLANK...
Page 74: ...INTENTIONALLY LEFT BLANK...
Page 76: ...INTENTIONALLY LEFT BLANK...
Page 80: ...INTENTIONALLY LEFT BLANK...
Page 82: ...INTENTIONALLY LEFT BLANK...
Page 84: ...INTENTIONALLY LEFT BLANK...
Page 111: ......